GE Multilin
L60 Line Phase Comparison System
8-37
8 THEORY OF OPERATION
8.2 SINGLE-POLE TRIPPING
8
If none of the fault types indicated above is determined, then three-phase fault conditions are checked to detect the pres-
ence of positive-sequence current and the absence of both zero-sequence and negative-sequence current. If these condi-
tions are met, then the
PHASE SELECT 3P
FlexLogic operand is asserted; otherwise, the
PHASE SELECT VOID
operand is
asserted, indicating that the phase selector failed to identify the fault type.
Finally, the states of the following additional FlexLogic operands are determined.
The phase selector operands are reset ½ cycle after the
OPEN POLE OP
FlexLogic operand is asserted or after delay
defined by the
PHASE SELECTOR RESET
setting (in Trip Output element) once the disturbance detector (50DD) initially oper-
ated.
Figure 8–30: PHASE SELECTOR LOGIC
OPERAND
DESCRIPTION
PHASE SELECT AG
Asserted when a phase A to ground fault is detected.
PHASE SELECT BG
Asserted when a phase B to ground fault is detected.
PHASE SELECT CG
Asserted when a phase C to ground fault is detected.
PHASE SELECT AB
Asserted when a phase A to B fault is detected.
PHASE SELECT BC
Asserted when a phase B to C fault is detected.
PHASE SELECT CA
Asserted when a phase C to A fault is detected.
PHASE SELECT ABG
Asserted when a phase A to B to ground fault is detected.
PHASE SELECT BCG
Asserted when a phase B to C to ground fault is detected.
PHASE SELECT CAG
Asserted when a phase C to A to ground fault is detected.
OPERAND
DESCRIPTION
PHASE SELECT SLG
Asserted if any of PHASE SELECT AG, PHASE SELECT BG, or PHASE SELECT CG
operands is active.
PHASE SELECT MULTI-P
Asserted if neither the PHASE SELECT SLG nor PHASE SELECT VOID operands are being
asserted.
837027A6.CDR
SRCn 50DD OP
OPEN POLE OP
SRCn VT FUSE FAIL OP
DISTANCE SOURCE:
AND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
SETTING
DELAY
SETTING
I_1
V_0
V_1
V_2
I_0
I_2
FLEXLOGIC OPERANDS
PHASE SELECT AG
RESET
START
PHASE SELECT
OR
PHASE SELECT BG
PHASE SELECT CG
PHASE SELECT AB
PHASE SELECT BC
PHASE SELECT CA
PHASE SELECT ABG
PHASE SELECT BCG
PHASE SELECT CAG
PHASE SELECT 3P
PHASE SELECT SLG
PHASE SELECT MULTI-P
PHASE SELECT VOID
4 cycles
t
RST
0
0
DELAY
0
0.5 cycles
PHASE SELECTOR
RESET DELAY
From the Trip Output element
Summary of Contents for L60
Page 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Page 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Page 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...