GE Multilin
L60 Line Phase Comparison System
5-55
5 SETTINGS
5.2 PRODUCT SETUP
5
The XCBR1 SYNCCHECK CLS setting is used to supervise a close command with a synchrocheck condition within XCBR
logical node. If a Close with SynchroCheck is requested (through a SelectWithValue service) and the SynchroCheck condi-
tion is not satisfied, a Negative Response (-Rsp) is issued with the REASON CODE of Blocked-by-synchrocheck.
The XCBR1 INTERLOCK OPN/CLS settings are used to assign an operand, which is linked into the EnaOpn or EnaCls
INTERLOCKED inputs respectively of the XCBR. When this operand is asserted, XCBR logical node inhibits execution of
the open and close commands respectively. If select before operate (SBO) with Extended Security is requested and Inter-
lock condition exists, the UR responds with a Negative response (-Rsp) with the Reason Code Blocked-by-interlocking.
The XCBR1 Pos ctlModel setting is used to select control model per IEC 61850-7-3. The following control models are sup-
ported by URs:
0 — Status only
1 — Direct control with normal security (direct-operate)
2 — SBO control with normal security (operate-once)
3 — Direct control with enhanced security (direct-operate)
4 — SBO control with enhanced security (operate-once)
See IEC 61850-7-2 for complete details on these control models.
The
XCBR1 P
os sboTimeout setting is used to select SBO timeout value. To be successful, the IEC 61850 "operate" com-
mand must be executed after the "select" command within the XCBR1 Pos sboTimeout setting value.
The disconnect switch configuration settings are shown below. Changes to these values will not take effect until the UR is
restarted:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
XSWI CONFIGURATION
The CLEAR XSWI1 OpCnt setting represents the disconnect switch operating counter. As disconnect switches operate by
opening and closing, the XSWI operating counter status attribute (OpCnt) increments with every operation. Frequent switch
operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XSWI1.
Since GSSE/GOOSE messages are multicast Ethernet by specification, they are not usually be forwarded by net-
work routers. However, GOOSE messages may be forwarded by routers if the router has been configured for VLAN
functionality.
XSWI
CONFIGURATION
XSWI1 ST.LOC OPERAND
Off
Range: FlexLogic operand
MESSAGE
XSWI2 ST.LOC OPERAND
Off
Range: FlexLogic operand
MESSAGE
XSWI3 ST.LOC OPERAND
Off
Range: FlexLogic operand
MESSAGE
XSWI24 ST.LOC OPERAND
Off
Range: FlexLogic operand
MESSAGE
CLEAR XSWI1 OpCnt:
No
Range: No, Yes
MESSAGE
CLEAR XSWI2 OpCnt:
No
Range: No, Yes
MESSAGE
CLEAR XSWI3 OpCnt:
No
Range: No, Yes
MESSAGE
CLEAR XSWI24 OpCnt:
No
Range: No, Yes
NOTE
Summary of Contents for L60
Page 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Page 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Page 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...