GE Multilin
L60 Line Phase Comparison System
5-37
5 SETTINGS
5.2 PRODUCT SETUP
5
j) DNP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
DNP PROTOCOL
DNP PROTOCOL
DNP CHANNELS
Range: see sub-menu below
MESSAGE
DNP ADDRESS:
1
Range: 0 to 65519 in steps of 1
MESSAGE
DNP NETWORK
CLIENT ADDRESSES
Range: see sub-menu below
MESSAGE
DNP TCP/UDP PORT
NUMBER: 20000
Range: 0 to 65535 in steps of 1
MESSAGE
DNP UNSOL RESPONSE
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
DNP UNSOL RESPONSE
TIMEOUT: 5 s
Range: 0 to 60 s in steps of 1
MESSAGE
DNP UNSOL RESPONSE
MAX RETRIES: 10
Range: 1 to 255 in steps of 1
MESSAGE
DNP UNSOL RESPONSE
DEST ADDRESS: 1
Range: 0 to 65519 in steps of 1
MESSAGE
DNP CURRENT SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP VOLTAGE SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP POWER SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP ENERGY SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP PF SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP OTHER SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP CURRENT DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP VOLTAGE DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP POWER DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP ENERGY DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP PF DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP OTHER DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP TIME SYNC IIN
PERIOD: 1440 min
Range: 1 to 10080 min. in steps of 1
Summary of Contents for L60
Page 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Page 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Page 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...