C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
APPENDIX C
C
•
Header.
•
Substation.
•
Communication.
•
IED section (one or more).
•
DataTypeTemplates.
The root file structure of an SCD file is illustrated below.
Figure C–6: SCD FILE STRUCTURE, SCL (ROOT) NODE
Like ICD files, the
Header
node identifies the SCD file and its version, and specifies options for the mapping of names to
signals.
The
Substation
node describes the substation parameters:
Figure C–7: SCD FILE STRUCTURE, SUBSTATION NODE
842791A1.CDR
SCL
Header (id, version, revision, toolID, nameStructure)
IED Section (IED 2)
Communication
IED Section (IED 1)
Substation
Other IED Sections
DataTypeTemplates
842792A1.CDR
Substation
EquipmentContainer
VoltageLevel
Function
PowerSystemResource
Power Transformer
GeneralEquipment
EquipmentContainer
Bay
Voltage
PowerSystemResource
SubFunction
GeneralEquipment
Summary of Contents for L60
Page 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Page 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Page 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...