GE Multilin
L60 Line Phase Comparison System
5-181
5 SETTINGS
5.5 GROUPED ELEMENTS
5
Figure 5–81: GROUND DIRECTIONAL SUPERVISION SCHEME LOGIC
5.5.6 POWER SWING DETECT
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
POWER SWING DETECT
POWER SWING
DETECT
POWER SWING
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
POWER SWING
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
POWER SWING
SHAPE: Mho Shape
Range: Mho Shape, Quad Shape
MESSAGE
POWER SWING
MODE: Two Step
Range: Two Step, Three Step
MESSAGE
POWER SWING
SUPV: 0.600 pu
Range: 0.050 to 30.000 pu in steps of 0.001
MESSAGE
POWER SW I2 SUPV ENAB:
Off
Range: FlexLogic operand
MESSAGE
POWER SWING
I2 SUPV: 0.2 pu
Range: 0.050 to 30.000 pu in steps of 0.001
MESSAGE
POWER SWING FWD
REACH: 50.00
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD FWD
REACH MID: 60.00
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD FWD
REACH OUT: 70.00
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING FWD
RCA: 75°
Range: 40 to 90° in steps of 1
MESSAGE
POWER SWING REV
REACH: 50.00
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD REV
REACH MID: 60.00
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD REV
REACH OUT: 70.00
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING REV
RCA: 75°
Range: 40 to 90° in steps of 1
V_0 > 5 volts
RUN
Zero-sequence
directional characteristic
837009A7.CDR
AND
OR
Co-ordinating time:
pickup = 1.0 cycle, reset = 1.0 cycle
SETTING
= V_0
= I_0
Distance Source
FLEXLOGIC OPERAND
OPEN POLE OP
TIMER
t
pickup
t
reset
FLEXLOGIC OPERAND
GND DIST Z2 DIR SUPN
Summary of Contents for L60
Page 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Page 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Page 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...