GE Multilin
L60 Line Phase Comparison System
5-147
5 SETTINGS
5.5 GROUPED ELEMENTS
5
Refer to the
Application of settings
chapter for the calculation examples for the phase comparison element.
Table 5–20: 87PC OSCILLOGRAPHY CHANNELS
CFG FILE LABEL
DESCRIPTION
X1: IA
Phase A of the F module CT bank
X2: IB
Phase B of the F module CT bank
X3: IC
Phase C of the F module CT bank
X#: IA
Phase A of the X module CT bank
X#: IB
Phase B of the X module CT bank
X#: IC
Phase C of the X module CT bank
87PC BKR1 Current
Effective mixed operating signal of breaker 1
87PC BKR1 POS
Positive current pulse for the first breaker
87PC BKR1 NEG
Negative current pulse for the first breaker
87PC BKR1 FDL
Low-set fault detection for the first breaker
87PC BKR1 FDH
High-set fault detection for the first breaker
87PC BKR2 Current
Effective mixed operating signal of BKK2
87PC BKR2 POS
Positive current pulse for the second breaker
87PC BKR2 NEG
Negative current pulse for the second breaker
87PC BKR2 FDL
Low-set fault detection for the second breaker
87PC BKR2 FDH
High-set fault detection for the second breaker
87PC POS
Positive current local pulse for both breakers
87PC NEG
Negative current local pulse for both breakers
87PC FDL
Low-set fault detection for both breakers
87PC FDH
High-set fault detection for both breakers
87PC Rx1P Voltage
Received pulse (voltage) on channel 1P
87PC Rx1P
Received pulse on channel 1P
87PC Rx1N Voltage
Received (voltage) on channel 1N
87PC Rx1N
Received pulse on channel 1N
87PC Rx2P Voltage
Received pulse (voltage) on channel 2P
87PC Rx2P
Received pulse on channel 2P
87PC Rx2N Voltage
Received pulse (voltage) on channel 2N
87PC Rx2N
Received pulse on channel 2N
87PC POS Aligned
Aligned (delayed) local positive pulse
87PC NEG Aligned
Aligned (delayed) local negative pulse
87PC Rx1P Aligned
Received and conditioned pulse on channel 1P
87PC Rx1N Aligned
Received and conditioned pulse on channel 1N
87PC Rx2P Aligned
Received and conditioned pulse on channel 2P
87PC Rx2N Aligned
Received and conditioned pulse on channel 2N
87PC POS Int Input
Input of the positive integrator
87PC NEG Int Input
Input of the negative integrator
87PC POS Integrator
Positive integrator in (degrees)
87PC NEG Integrator
Negative integrator in (degrees)
87PC Trip
CT/VT module to CPU trip pulse
Tx Pos
Transmit signal per 87PC logic
Tx Neg
Transmit signal per 87PC logic
FDH Aligned
Summary of Contents for L60
Page 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Page 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Page 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...