6-24
L60 Line Phase Comparison System
GE Multilin
6.4 RECORDS
6 ACTUAL VALUES
6
6.4.5 BREAKER MAINTENANCE
PATH: ACTUAL VALUES
RECORDS
MAINTENANCE
BREAKER 1(2)
There is an identical menu for each of the breakers. The
BKR 1 ARCING AMP
values are in units of kA
2
-cycles. Refer to the
COMMANDS
CLEAR RECORDS
menu for clearing breaker arcing current records. The
BREAKER OPERATING TIME
is
defined as the slowest operating time of breaker poles that were initiated to open.
BREAKER 1
BKR 1 ARCING AMP
A:
0.00 kA2-cyc
MESSAGE
BKR 1 ARCING AMP
B:
0.00 kA2-cyc
MESSAGE
BKR 1 ARCING AMP
C:
0.00 kA2-cyc
MESSAGE
BKR 1 OPERATING TIME
A: 0
ms
MESSAGE
BKR 1 OPERATING TIME
B: 0
ms
MESSAGE
BKR 1 OPERATING TIME
C: 0
ms
MESSAGE
BKR 1 OPERATING
TIME:
0 ms
Summary of Contents for L60
Page 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Page 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Page 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...