GE Multilin
L60 Line Phase Comparison System
5-281
5 SETTINGS
5.6 CONTROL ELEMENTS
5
Figure 5–140: OPEN POLE DETECTOR LOGIC (Sheet 2 of 2)
g) THERMAL OVERLOAD PROTECTION
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
THERMAL OVERLOAD PROTECTION
THERMAL
PROTECTION 1(2)
THERMAL
PROTECTION 1
THERMAL PROTECTION 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
THERMAL PROTECTION 1
SOURCE: SRC1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
THERMAL PROTECTION 1
BASE CURR: 0.80 pu
Range: 0.20 to 3.00 pu in steps of 0.01
MESSAGE
THERMAL PROTECTION 1
k FACTOR: 1.10
Range: 1.00 to 1.20 in steps of 0.05
MESSAGE
THERM PROT 1 TRIP
TIME CONST: 45 min.
Range: 0 to 1000 min. in steps of 1
MESSAGE
THERM PROT 1 RESET
TIME CONST: 45 min.
Range: 0 to 1000 min. in steps of 1
MESSAGE
THERM PROT 1 MINIM
RESET TIME: 20 min.
Range: 0 to 1000 min. in steps of 1
MESSAGE
THERM PROT 1 RESET:
Off
Range: FlexLogic operand
MESSAGE
THERM PROT 1 BLOCK:
Off
Range: FlexLogic operand
MESSAGE
THERMAL PROTECTION 1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
THERMAL PROTECTION 1
EVENTS: Disabled
Range: Disabled, Enabled
OR
837038A2.CDR
OR
OR
OR
OR
XOR
FLEXLOGIC OPERAND
TRIP PHASE A
PHASE A
TIMER
0.5 cycles
0
ENABLED
from the trip output element
OR
FLEXLOGIC OPERAND
TRIP PHASE B
PHASE B
TIMER
0.5 cycles
0
from the trip output element
OR
FLEXLOGIC OPERAND
TRIP PHASE C
PHASE C
TIMER
0.5 cycles
0
from the trip output element
AND
AND
AND
TIMER
0
20 ms
TIMER
0
20 ms
TIMER
0
20 ms
FLEXLOGIC OPERAND
OPEN POLE BLK N
FLEXLOGIC OPERAND
OPEN POLE OP A
Φ
FLEXLOGIC OPERAND
OPEN POLE BLK AB
FLEXLOGIC OPERAND
OPEN POLE OP B
Φ
FLEXLOGIC OPERAND
OPEN POLE BLK BC
FLEXLOGIC OPERAND
OPEN POLE OP C
Φ
FLEXLOGIC OPERAND
OPEN POLE BLK CA
FLEXLOGIC OPERAND
OPEN POLE OP
AND
AND
AND
from open pole logic sheet 1
from open pole logic sheet 1
from open pole logic sheet 1
from open pole logic sheet 1
SETTING
= Accelerated
= Traditional
Open Pole Mode
Summary of Contents for L60
Page 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Page 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Page 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...