5-288
L60 Line Phase Comparison System
GE Multilin
5.6 CONTROL ELEMENTS
5 SETTINGS
5
5.6.11 AUTORECLOSE
PATH: SETTINGS
CONTROL ELEMENTS
AUTORECLOSE
AUTORECLOSE
AUTORECLOSE
AR FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
AR MODE:
Mode 1 (1 & 3 Pole)
Range: Mode 1(1 & 3 Pole), Mode 2 (1 Pole), Mode 3 (3
Pole-A), Mode 4 (3 Pole-B)
MESSAGE
Mode 1 Activation:
Off
Range: FlexLogic operand
MESSAGE
Mode 2 Activation:
Off
Range: FlexLogic operand
MESSAGE
Mode 3 Activation:
Off
Range: FlexLogic operand
MESSAGE
Mode 4 Activation:
Off
Range: FlexLogic operand
MESSAGE
AR MAX NUMBER OF
SHOTS: 2
Range: 1, 2, 3, 4
MESSAGE
AR INITIATE MODE:
Protection AND CB
Range: Protection AND CB, Protection Only
MESSAGE
AR BLOCK BKR1:
Off
Range: FlexLogic operand
MESSAGE
AR CLOSE TIME BKR 1:
0.10 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR BKR MAN CLOSE:
Off
Range: FlexLogic operand
MESSAGE
AR BLK TIME UPON MAN
CLS:
10.00 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 1P INIT:
Off
Range: FlexLogic operand
MESSAGE
AR 3P INIT:
Off
Range: FlexLogic operand
MESSAGE
AR 3P TD INIT:
Off
Range: FlexLogic operand
MESSAGE
AR MULTI-P FAULT:
Off
Range: FlexLogic operand
MESSAGE
BKR ONE POLE OPEN:
Off
Range: FlexLogic operand
MESSAGE
BKR 3 POLE OPEN:
Off
Range: FlexLogic operand
MESSAGE
AR 3-P DEAD TIME 1:
0.50 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 3-P DEAD TIME 2:
1.20 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 3-P DEAD TIME 3:
2.00 s
Range: 0.00 to 655.35 s in steps of 0.01
Summary of Contents for L60
Page 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Page 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Page 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...