5-84
L60 Line Phase Comparison System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The user-programmable pushbutton logic is shown below.
Figure 5–16: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2)
S
R
Non-volatile latch
Latch
OR
OR
OR
OR
OR
OR
AND
SETTING
= Enabled
= Latched
Function
= Self-Reset
SETTING
Off = 0
Remote Lock
SETTING
Off = 0
Local Lock
SETTING
Off = 0
Set
SETTING
Off = 0
Reset
SETTING
= Enabled
= Disabled
Autoreset Function
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
FLEXLOGIC OPERAND
PUSHBUTTON 1 OFF
TIMER
200 ms
0
AND
AND
AND
AND
AND
TIMER
50 ms
0
TIMER
50 ms
0
SETTING
Autoreset Delay
T
PKP
0
TIMER
200 ms
0
AND
AND
SETTING
Drop-Out Timer
T
RST
0
PUSHBUTTON ON
To user-programmable
pushbuttons logic
sheet 2, 842024A2
LATCHED
LATCHED/SELF-RESET
To user-programmable
pushbuttons logic
sheet 2, 842024A2
842021A3.CDR
SETTING
Hold
T
PKP
0
Summary of Contents for L60
Page 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Page 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Page 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...