GE Multilin
L60 Line Phase Comparison System
6-19
6 ACTUAL VALUES
6.3 METERING
6
6.3.5 FLEXELEMENTS
PATH: ACTUAL VALUES
METERING
FLEXELEMENTS
FLEXELEMENT 1(8)
The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
6.3.6 IEC 61580 GOOSE ANALOG VALUES
PATH: ACTUAL VALUES
METERING
IEC 61850 GOOSE ANALOGS
The L60 Line Phase Comparison System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. See the
Order Codes
section of chap-
ter 2 for details.
The IEC 61850 GGIO3 analog input data points are displayed in this menu. The GGIO3 analog data values are received
via IEC 61850 GOOSE messages sent from other devices.
FLEXELEMENT 1
FLEXELEMENT 1
OpSig: 0.000 pu
Table 6–2: FLEXELEMENT BASE UNITS
BREAKER ARCING AMPS
(Brk X Arc Amp A, B, and C)
BASE = 2000 kA
2
cycle
dcmA
BASE = maximum value of the
DCMA INPUT MAX
setting for the two transducers configured
under the +IN and –IN inputs.
FREQUENCY
f
BASE
= 1 Hz
PHASE ANGLE
BASE
= 360 degrees (see the UR angle referencing convention)
POWER FACTOR
PF
BASE
= 1.00
RTDs
BASE = 100°C
SOURCE CURRENT
I
BASE
= maximum nominal primary RMS value of the +IN and –IN inputs
SOURCE POWER
P
BASE
= maximum value of V
BASE
I
BASE
for the +IN and –IN inputs
SOURCE VOLTAGE
V
BASE
= maximum nominal primary RMS value of the +IN and –IN inputs
SYNCHROCHECK
(Max Delta Volts)
V
BASE
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
Z
BASE
Z
BASE
= PhaseVTSecondary / PhaseCTSecondary, where PhaseVTSecondary and
PhaseCTSecondary are the secondary nominal voltage and the secondary nominal current of the
distance source. In case multiple CT inputs are summed as one source current and mapped as
the distance source, use the PhaseCTSecondary value from the CT with the highest primary
nominal current.
Distance source is specified in setting under
SETTINGS > GROUPED ELEMENTS > SETTING
GROUP 1(6) > DISTANCE
.
PhaseVTSecondary and PhaseCTSecondary are specified in setting under
SETTINGS > SYSTEM
SETUP > AC INPUTS
.
IEC 61850
GOOSE ANALOGS
ANALOG INPUT
1
0.000
MESSAGE
ANALOG INPUT
2
0.000
MESSAGE
ANALOG INPUT
3
0.000
MESSAGE
ANALOG INPUT 32
0.000
Summary of Contents for L60
Page 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Page 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Page 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...