5-196
L60 Line Phase Comparison System
GE Multilin
5.5 GROUPED ELEMENTS
5 SETTINGS
5
IAC CURVES:
The curves for the General Electric type IAC relay family are derived from the formulae:
,
(EQ 5.12)
where:
T
= operate time (in seconds),
TDM
= Multiplier setting,
I
= Input current,
I
pkp
= Pickup Current setting,
A to
E
=
constants,
t
r
= characteristic constant, and
T
RESET
= reset time in seconds (assuming energy capacity is 100%
and
RESET
is “Timed”)
Table 5–26: GE TYPE IAC INVERSE TIME CURVE CONSTANTS
IAC CURVE SHAPE
A
B
C
D
E
T
R
IAC Extreme Inverse
0.0040
0.6379
0.6200
1.7872
0.2461
6.008
IAC Very Inverse
0.0900
0.7955
0.1000
–1.2885
7.9586
4.678
IAC Inverse
0.2078
0.8630
0.8000
–0.4180
0.1947
0.990
IAC Short Inverse
0.0428
0.0609
0.6200
–0.0010
0.0221
0.222
Table 5–27: IAC CURVE TRIP TIMES
MULTIPLIER
(TDM)
CURRENT (
I
/
I
pickup
)
1.5
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
IAC EXTREMELY INVERSE
0.5
1.699
0.749
0.303
0.178
0.123
0.093
0.074
0.062
0.053
0.046
1.0
3.398
1.498
0.606
0.356
0.246
0.186
0.149
0.124
0.106
0.093
2.0
6.796
2.997
1.212
0.711
0.491
0.372
0.298
0.248
0.212
0.185
4.0
13.591
5.993
2.423
1.422
0.983
0.744
0.595
0.495
0.424
0.370
6.0
20.387
8.990
3.635
2.133
1.474
1.115
0.893
0.743
0.636
0.556
8.0
27.183
11.987
4.846
2.844
1.966
1.487
1.191
0.991
0.848
0.741
10.0
33.979
14.983
6.058
3.555
2.457
1.859
1.488
1.239
1.060
0.926
IAC VERY INVERSE
0.5
1.451
0.656
0.269
0.172
0.133
0.113
0.101
0.093
0.087
0.083
1.0
2.901
1.312
0.537
0.343
0.266
0.227
0.202
0.186
0.174
0.165
2.0
5.802
2.624
1.075
0.687
0.533
0.453
0.405
0.372
0.349
0.331
4.0
11.605
5.248
2.150
1.374
1.065
0.906
0.810
0.745
0.698
0.662
6.0
17.407
7.872
3.225
2.061
1.598
1.359
1.215
1.117
1.046
0.992
8.0
23.209
10.497
4.299
2.747
2.131
1.813
1.620
1.490
1.395
1.323
10.0
29.012
13.121
5.374
3.434
2.663
2.266
2.025
1.862
1.744
1.654
IAC INVERSE
0.5
0.578
0.375
0.266
0.221
0.196
0.180
0.168
0.160
0.154
0.148
1.0
1.155
0.749
0.532
0.443
0.392
0.360
0.337
0.320
0.307
0.297
2.0
2.310
1.499
1.064
0.885
0.784
0.719
0.674
0.640
0.614
0.594
4.0
4.621
2.997
2.128
1.770
1.569
1.439
1.348
1.280
1.229
1.188
6.0
6.931
4.496
3.192
2.656
2.353
2.158
2.022
1.921
1.843
1.781
8.0
9.242
5.995
4.256
3.541
3.138
2.878
2.695
2.561
2.457
2.375
10.0
11.552
7.494
5.320
4.426
3.922
3.597
3.369
3.201
3.072
2.969
IAC SHORT INVERSE
0.5
0.072
0.047
0.035
0.031
0.028
0.027
0.026
0.026
0.025
0.025
1.0
0.143
0.095
0.070
0.061
0.057
0.054
0.052
0.051
0.050
0.049
2.0
0.286
0.190
0.140
0.123
0.114
0.108
0.105
0.102
0.100
0.099
4.0
0.573
0.379
0.279
0.245
0.228
0.217
0.210
0.204
0.200
0.197
6.0
0.859
0.569
0.419
0.368
0.341
0.325
0.314
0.307
0.301
0.296
8.0
1.145
0.759
0.559
0.490
0.455
0.434
0.419
0.409
0.401
0.394
10.0
1.431
0.948
0.699
0.613
0.569
0.542
0.524
0.511
0.501
0.493
T
TDM
A
B
I I
pkp
C
–
------------------------------
D
I I
pkp
C
–
2
--------------------------------------
E
I I
pkp
C
–
3
--------------------------------------
+
+
+
=
T
RESET
TDM
t
r
1
I I
pkp
2
–
--------------------------------
=
Summary of Contents for L60
Page 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Page 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Page 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...