-50-
6.2.10 Model 210 (TS2) Turbidity Sensor
TS2 Detector wire connections to Messenger
Terminal
#
Wire
Color
Cable
ID
Signal
1
Black
TS2 module
(–) Direct Beam Detector
2
Red
TS2 module
(+) Direct BeamDetector
3
White
TS2 module
Shield (ground)
4
Green
TS2 module
(–) 12 Degree Detector
5
Yellow
TS2 module
(+) 12 Degree Detector
6
-
-
-
7
8
9
Lamp connections must be connected to the Lamp Supply Control Board in the
Messenger PC
Terminal
3
Lamp (Orange) (–)
4
Lamp (Green) (+)
The Model 210 lamp should not be powered directly from the Messenger module.
Summary of Contents for MONITEK MESSENGER
Page 1: ...MESSENGER PC TRANSMITTER User s manual Release 1 2 September 15 2015...
Page 11: ...9 Installation dimensions for Messenger PC transmitter in fiberglass enclosure...
Page 12: ...10 Installation dimensions for Messenger PC transmitter in stainless steel enclosure...
Page 13: ...11 1 3 2 Transmitter and Sensor Wiring System Layout and Interconnections details...
Page 14: ...12...