MCT-MC
4.3
FDC MCT-MC
- 160 -
Appendix
The first 5 registers of the program (header step) contain specific settings related to the program. These
include the program number, hold back band, ramp units and dwell units.
Register
Address
Parameter Description
Data
*D
Range
*E
*F
Type
Low
High
Unit
86
(0x0056)
Program Selected for View
W
9
9
-
87
(0x0057)
Hold Back Band
W
*E1
*E1
-
88
(0x0058)
89
(0x0059)
Ramp Units
W
*E2
*E2
-
90
(0x005A)
Dwell Units
W
*E3
*E3
-
The following 10 registers of the automatic program contain the data for step 1 of the program.
Register
Address
Parameter Description
Data
D
Range
*E
*F
Type
Low
High
Unit
91
(0x005B)
Step Number
*
W
0
63
-
92
(0x005C)
Step Type
W
*E4
*E4
-
93
(0x005D)
Ramp Target Setpoint
W
-32768
32767
PV
94
(0x005E)
Ramp Time or Ramp Rate
W
0
5999
-
95
(0x005F)
Event Selections 1, 2, 3
W
*E5
*E5
-
96
(0x0060)
Holdback Type
W
*E6
*E6
-
97
(0x0061)
Dwell Time
W
0
9999
-
98
(0x0062)
Jump Step
W
0
63
-
99
(0x0063)
Jump Cycles
W
1
9999
-
100
(0x0064)
Final Setpoint
W
-32768
32767
PV
**
The
Step Number
must be offset by -1 when writing step data to the MC. Steps 1-64 will be sent with the
step number as a value of 0-63 (-1 offset).
All remaining steps of the program follow the same format and data structure as is represented for step
one above. Each step of the program is downloaded to the same registers (91 to 100). The step number
in register 91 designates the step that the data is for on each write command. Since few if any programs
will contain the maximum of 64 steps, it is only necessary to write the step data for the number steps
used in the automatic program.
Notes:
*D
W Specifies write only data.
*E1
Parameter
Value
Temperature
Units °C
Temperature
Units °F
Process
Units
Range Low
1
1
1
Range High
555
999
999
Summary of Contents for MCT-MC 4.3
Page 1: ...MCT MC 4 3 User Manual MCT MC 4 3 User Manual Rev A February 2018...
Page 176: ...MCT MC4 3 FDC MCT MC 176 Appendix...
Page 177: ...MCT MC4 3 Appendix 177 FDC MCT MC Open Frame Power Supply Specifications...
Page 178: ...MCT MC4 3 FDC MCT MC 178 Appendix...
Page 179: ...MCT MC4 3 Appendix 179 FDC MCT MC A 6 Power On Delay Relay Specifications GE1A C10HA110...
Page 180: ...MCT MC4 3 FDC MCT MC 180 Appendix...