Alarm Codes and Troubleshooting
Alarm Monitor Description
Explanation/Corrective Action
“tagname”
outputs 1 and 2 incorrectly
configured.
(error code 4) Indicates that the control loop configuration for the loop control
indicated by “tagname” is not valid and must be corrected to clear the alarm.
Check and correct setup values of output 2, PB, TI and output 1. If output 2
is required for cooling control, the control should use PID mode (PB > 0, TI
> 0 ) and output 1 should use reverse mode (heat action), otherwise, don't
use output 2 for cooling control.
“tagname”
sensor break
Check sensor wiring for the loop control indicated by
“tagname”
. Verify lead
connections. If sensor requires power, verify power to sensor.