MCT-MC
4.3
FDC MCT-MC
- 154 -
Appendix
Read 2 bytes from serial
port and check value of
second byte
Read
Command
(0x03)
NO
Read 1 byte from serial
port and obtain number of
data bytes in message.
YES
Write
Command
(0x06/10)
NO
Exception
Response
(0x8_)
YES
YES
Read remaining 8 bytes
from serial port to obtain
complete message.
Read remaining 3 bytes
from serial port to obtain
complete message.
Read in number of data
bytes from message plus 2
additional CRC bytes.
Calculate the CRC for the
message and compare to
CRC received.
NO
YES
CRC’s
match
Disregard message
(transmission error)
Enter recovery mode and resend command message in
attempt to get valid response and/or alert operator of a
communication failure in order to take appropriate action.
Received message is valid.
If the message was a read
response, the data can be
extracted and converted
for use within the software.
If the message was a write
response, the MC executed
the command.
NO
Was it an
exception
response?
YES