Configuring the MCT-MC
The
Continue automated program from last SP
selection will resume the program from where it left off with
the last set point set by the program at the time of power failure.
The
Continue automated program from PV
selection will resume the program using the current process value
at the time power is restored as the set point.
The
Static mode
selection will terminate the automated program and return the loop control to the single set
point mode of operation using the previous set point value prior to starting the automatic program. In addition,
any outputs configured as events will also be returned to their previous on/off prior to starting the program.
NOTE:
The MC does not support the P41/B42 “Off Mode” recovery option. This selection is not available
through the MC configuration.
4.3.32 Communication Mode
The Communication Mode selection is used to specify how the loop control responds to a loss of
communications with the MC display. The communication mode selections are mutually exclusive, i.e.,
selecting one will turn off the other. Once the desired mode has been selected, press the “Done” button to set
the communication mode for the loop control board and return to the main Loop Configuration screen.
NOTE:
It is recommended that the “Safety” communication mode be used to insure all outputs are turned off
(linear outputs set to 0%) in the event of a loss of communications between the MC and the loop
control.
Summary of Contents for MCT-MC 4.3
Page 1: ...MCT MC 4 3 User Manual MCT MC 4 3 User Manual Rev A February 2018...
Page 176: ...MCT MC4 3 FDC MCT MC 176 Appendix...
Page 177: ...MCT MC4 3 Appendix 177 FDC MCT MC Open Frame Power Supply Specifications...
Page 178: ...MCT MC4 3 FDC MCT MC 178 Appendix...
Page 179: ...MCT MC4 3 Appendix 179 FDC MCT MC A 6 Power On Delay Relay Specifications GE1A C10HA110...
Page 180: ...MCT MC4 3 FDC MCT MC 180 Appendix...