MCT-MC
4.3
Configuring the MCT-MC
- 39 -
FDC MCT-MC
MC Function
Runtime Menu Location
Description
Security Settings
Security
Notifications
view/set security rights, view audit trails, user log on
view security and audit status
NOTE:
If security is enabled, but system security is then
disabled through this item, the user will be unable to log
on. Default security (operator level) access will be used.
This allows audit trails to be active while hiding all user
security features.
With security menu disabled, audit trail files are
accessible via Log/USB File Utilities or temporarily re-
enable security menu to gain access to the audit files.
Automatic Program
Control/Recovery
Program
Device\Settings\Offline\Set\Recovery
Notifications
view, create, edit and run automatic ramp/soak programs
set power recovery mode
view program status
NOTE:
When disabled, all program items and menus will
be removed from the runtime application. The user will
be unable to access or start programs via the interface.
Data Logging
Data\Data
Notifications
enable/disable data logging, select points for logging,
access to historical viewer, FTP and USB File utilities
view data log status, length and interval
NOTE:
If data logging is set to log on program operation
or when the MC starts and this menu is then disabled,
data logging will be disabled. This menu item must
remain visible in order for the built in data logging of the
MC to function.
The USB File utilities will not be accessible to copy or
delete data, alarm, audit or program files.
Data Log Viewer
Data\Chart
access to view historical data log files
Annotations
Data\View\Annotation
access to add and view operator annotations to data files
Digital Signatures
Data\View\Signature
access to view and add digital signature to data log file
File Utilities
Data\Utilities\USB
access to copy/delete alarm, audit, program and data log
files
Note:
Alarm, audit and data files may be transferred via
FTP if unit is so configured.
FTP/WAN Settings
Data\Utilities\FTP/WAN
access to view/configure FTP file transfer settings
NOTE:
Once the FTP is configured for Auto Backup in
the runtime application, this menu item can be disabled
and hidden from the operator so that OEM configuration
is preserved and can not be accessed or altered. The
Auto Backup to the FTP Server would occur as
configured.
Loop Manual Mode
View\Loop
access to placing the loop in manual and setting a fixed
percentage of output
Loop PID Tuning
Device\Settings\View\Tuning
access loop tuning screen
NOTE:
With loop PID tuning disabled, the user will also
loose the ability to place the loop in auto tune.
Summary of Contents for MCT-MC 4.3
Page 1: ...MCT MC 4 3 User Manual MCT MC 4 3 User Manual Rev A February 2018...
Page 176: ...MCT MC4 3 FDC MCT MC 176 Appendix...
Page 177: ...MCT MC4 3 Appendix 177 FDC MCT MC Open Frame Power Supply Specifications...
Page 178: ...MCT MC4 3 FDC MCT MC 178 Appendix...
Page 179: ...MCT MC4 3 Appendix 179 FDC MCT MC A 6 Power On Delay Relay Specifications GE1A C10HA110...
Page 180: ...MCT MC4 3 FDC MCT MC 180 Appendix...