714
Upgrade and Maintenance Manual
TX300 S8 / RX350 S8
Converting a tower server to a rack server
15.3 Removing the accessible drive cage
Figure 557: Detaching the accessible drive cage (A)
Ê
Remove two screws from the bottom side of the server as shown.
Ê
Bring the server back to its horizontal position.
I
At least two people are needed to turn over a fully equipped server.
Remove hard disk drives and power supply modules in order to
facilitate the task.