TX300 S8 / RX350 S8
Upgrade and Maintenance Manual
727
Converting a tower server to a rack server
15.6 Removing glider feet
Figure 570: Removing glider feet
Ê
Using a slotted screw driver, slightly pry up on each glider foot until it
detaches.
Ê
Bring the server back to its horizontal position.
I
At least two people are needed to turn over a fully equipped server.
Remove hard disk drives and power supply modules in order to
facilitate the task.
15.7 Preparing the intrusion switch
Ê
Remove the intrusion switch module as described in section
"Removing the
intrusion switch cable" on page 762
.
Ê
Attach a rubber bumper (C26192-Y26-C43) to the front intrusion switch and
reinstall the intrusion switch module as described in section
"Installing the
intrusion switch cable" on page 765
.
Summary of Contents for PRIMERGY RX350 S8
Page 6: ...Upgrade and Maintenance Manual TX300 S8 RX350 S8 ...
Page 44: ...44 Upgrade and Maintenance Manual TX300 S8 RX350 S8 Before you start ...
Page 160: ...160 Upgrade and Maintenance Manual TX300 S8 RX350 S8 Basic software procedures ...
Page 182: ...182 Upgrade and Maintenance Manual TX300 S8 RX350 S8 Power supply ...
Page 320: ...320 Upgrade and Maintenance Manual TX300 S8 RX350 S8 Hard disk drives solid state drives ...
Page 344: ...344 Upgrade and Maintenance Manual TX300 S8 RX350 S8 Fans ...
Page 484: ...484 Upgrade and Maintenance Manual TX300 S8 RX350 S8 Main memory ...
Page 528: ...528 Upgrade and Maintenance Manual TX300 S8 RX350 S8 Processors ...
Page 644: ...644 Upgrade and Maintenance Manual TX300 S8 RX350 S8 Front panel and external connectors ...
Page 792: ...792 Upgrade and Maintenance Manual TX300 S8 RX350 S8 Appendix ...