3-10. SIGNAL AMPLIFIER
MODEL: UTY-VSGXZ1
If the total length of transmission line exceeds 500 m, or the number of elements exceeds 64
units, Signal Amplifier will be necessary to use.
● Transmission line length can be extended up to 3600 m with multiple signal
amplifier.
● Up to 8 Signal Amplifier (Filter mode is OFF) can be installed in 1 VRF
network system.
● Up to 32 Signal Amplifier (Filter mode is ON) can be installed in 1 VRF
network system.
● When installing 321 or more indoor units, install 1 Signal amplifier (Filter
mode is ON) for every 64 indoor units. (However, only when VR-II Series is installed.)
● To prevent the drop of signal level by taking distance of length or quantity of unit in VRF network with
installing signal amplifier, signal level can be recovered.
ELECTRICAL WIRING
z
Except in the case of V and S SeriesI
(Indoor unit is installed 320 units or less)
CH A
CH B
X1
X2
X1
X2
L
N
TRANSMISSION
POWER
SUPPLY
NO HIGH VOLTAGE
IN/U-
OUT/U
OTHER
CYCLE
MULTI
OUT/U
X1
X2
TRANS-
MISSION
X1
X2
TRANS-
MISSION
X1
X2
Z1
Z2 H1 H2
1Ø 50/60 Hz
220-240 V
FUSE (3 A)
SWITCH
Segment A
Segment B
TERMINAL
RESISTOR*
TERMINAL
RESISTOR*
(DIP SW setting)
Transmission Line
OUTDOOR UNIT
(MASTER UNIT)
TO SLAVE
UNIT
INDOOR UNIT
INDOOR UNIT
SIGNAL AMPLIFIER
- (05 - 189) -
C
O
N
TRO
L
SY
ST
EM
C
O
N
TRO
L
SY
ST
EM
Summary of Contents for AB* A12GATH
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...
Page 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...
Page 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...
Page 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...
Page 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...
Page 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...
Page 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...
Page 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...
Page 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...
Page 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...
Page 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...
Page 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...
Page 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...
Page 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...
Page 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...
Page 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...
Page 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...
Page 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...
Page 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...
Page 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...
Page 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...
Page 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...
Page 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...
Page 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...