CONTROL AND MONITORING ITEMS
NOTE:
For detailed information, check the Interface Specification.
Item
Function
Description
Indoor Unit
Control
(Individual /
Batch)
ON/OFF Command
Start / Stop operation
Operation Mode Setting
Cooling / Heating / Auto / Fan / Dry
Temperature Setting
Set room temperature
Airflow Mode Setting
Set airflow
Set Point Temperature Limit Setting
Set room temperature lower limit (for cooling
mode) & room temperature upper limit (for
heating mode)
Thermostat Off setting
Thermostat off
(Only one controller in VRF Network System can
do this)
Centrally Control (Filter Reset)
Prohibition of filter sign reset of remote controller
Centrally Control (All Mode )
Prohibition of all mode of remote controller
Centrally Control (Timer Mode)
Prohibition of timer mode of remote controller
Centrally Control (Set Temperature Mode) Prohibition of set temperature mode of remote
controller
Centrally Control (ON/OFF Mode)
Prohibition of ON/OFF mode of remote controller
Centrally Control (ON Mode)
Prohibition of ON mode of remote controller
Centrally Control (Operation Mode)
Prohibition of operation mode of remote controller
Indoor Unit
Control
(Individual)
Filter Sign Reset
Set filter sign reset command
Antifreeze Setting
Set antifreeze command
Energy Save Mode Setting
Set energy save command
Indoor Unit
Control
(Batch)
Emergency STOP Setting
Set Emergency STOP command
Time Setting
Set time setting command
(The controllers those are connected in VRF
Network System are an object)
Indoor Unit
Monitoring
(Individual)
ON/OFF Status
ON / OFF status
Operation Mode Setting Status
Heating / Cooling / Auto / Fan / Dry mode status
Temperature Setting Status
Room set temperature status
Airflow Mode Setting Status
Airflow mode status
Set Point Temperature Limit Status
Room set temperature limit status
Thermostat Off Setting Status
Thermostat off set value status
Centrally Control (Filter Reset) Status
Remote controller filter reset prohibition status
Centrally Control (All Mode ) Status
Remote controller all mode prohibition status
Centrally Control (Timer Mode) Status
Remote controller timer mode prohibition status
Centrally Control (Set Temperature) Status Remote controller set temp. prohibition status
Centrally Control (ON/OFF ) Status
Remote controller ON / OFF prohibition status
Centrally Control (ON ) Status
Remote controller ON prohibition status
Centrally Control (Operation ) Status
Remote controller operation prohibition status
Antifreeze Setting Status
Antifreeze set status
Energy Save Mode Setting Status
Energy save mode set status
Filter Sign Reset Status
Filter sign reset status
Room Temperature Status
Room temperature status
Error code Status
Only one Error code status can be monitored
Operation Mode restriction Status
Restriction item (*1) can be monitored
Indoor Unit
Monitoring
(Batch)
Maintenance Mode Status
Maintenance status
Emergency STOP Setting Status
Emergency STOP setting status
Outdoor Unit
Monitoring
(Individual)
Error code Status
Error code status
Convertor Unit
Monitoring
(Individual)
Error code Status
Error code status
*1: All operation setting, Timer setting, Room temperature setting, Operation mode setting, ON/OFF operation, Filter reset
operation, On operation setting.
- (05 - 163) -
C
O
N
TRO
L
SY
ST
EM
C
O
N
TRO
L
SY
ST
EM
Summary of Contents for AB* A12GATH
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...
Page 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...
Page 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...
Page 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...
Page 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...
Page 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...
Page 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...
Page 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...
Page 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...
Page 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...
Page 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...
Page 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...
Page 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...
Page 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...
Page 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...
Page 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...
Page 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...
Page 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...
Page 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...
Page 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...
Page 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...
Page 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...
Page 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...
Page 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...