4-2. POWER SUPPLY CABLE WIRING
POWER SUPPLY CABLE SPECIFICATIONS
Use a separate power supply for the outdoor unit and indoor unit.
z
Outdoor unit
Model
Recommended cable size
(mm
2
)
Fuse capacity
(A)
Breaker for
leakage current
Remarks
Power cable Earth cable
AJ
072LELAH
6
6
20
100mA 0.1sec
or less
AJ
090LELAH
6
6
20
AJ
108LELAH
6
6
25
●
Select wire size base on the value of MCA (Minimum Circuit Ampacity) and TOCA (Total
Value of Each Over Current Set). In the table of "3.OUTDOOR UNITS",example of wiring
specification for outdoor unit is given.
●
Select circuit breaker for outdoor unit based on the value of MCA of "3.OUTDOOR UNITS".
The breaker should not operate when starting current is generated.
z
Indoor unit
Model
Recommended
cable size (mm
2
)
Fuse capacity
(A)
Breaker for
leakage current
Remarks
All models
2.5
20
Refer to Table B 230V~ 50Hz
2Wire + ground
Refer to the table for the breaker specifications of each installation condition. Perform the
power crossover wiring within the range of the same refrigerant system.When the crossover
wiring is done, make a connection for indoor unit to satisfy conditions Table A and Table B
below.
Table A. Current breaker requirements
Model
MCA
(A)
Fuse capacity
(A)
All models
*1
20
MCA : Minimum Circuit Ampacity
*1 : Refer chapter4 2.ELECTRIC CHARACTERISTICS
When the power crossover wiring is done, make it so that the total of the MCA of the
connected indoor units does not exceed the 15 A.
If the capacity of connected indoor units exceeds the upper limit, either add breakers or use a
breaker with a greater capacity.
Table B. Earth leakage breaker requirements
Breaker capacity
Maximum connectable indoor unit
30 mA, 0.1 sec or less
30 or less
●
Select cable size base on the value of total MCA of the indoor units connected. and if
necessary divided the system which the total MCA of the indoor units connected must be
smaller than 15 (A). The indoor units shall be connected up whthin refrigerant system.
● In order to be influenced of a breaker stop, please divide a power supply circuit for every
refrigerant system.
●
Please attach at least one breaker per refrigerant system.
●
Please design the power supply circuit to keep the voltage drop within 2%.
- (06 - 43) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AB* A12GATH
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...
Page 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...
Page 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...
Page 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...
Page 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...
Page 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...
Page 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...
Page 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...
Page 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...
Page 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...
Page 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...
Page 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...
Page 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...
Page 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...
Page 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...
Page 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...
Page 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...
Page 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...
Page 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...
Page 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...
Page 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...
Page 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...
Page 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...
Page 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...