PRECAUTION
z
About fresh air intake kit
•The Fresh Air Intake Kit can be installed onto cassette type air conditioners.
•
The volume of ventilated air provided by the Fresh Air Intake Kit may be unable to fulfill ventilation
regulations in all countries.
On such occasions we ask that this kit be used along with Energy recovery ventilators.
• When intaking outside air please ensure correct air-conditioning design as based on air-
conditioning load calculations.
As outside air is not being processed an increase in outside air load can affect air conditioning.
z
Installation location
• Area that generate substances that adversely affect the equipment, such as sulfuric
gas,chlorine gas,add,or alkali it will cause the copper pipes and brazed joints to corrode,which
can cause refrigerant leakage.
• Area with high salt content,such as at the seaside. It will deteriorate metal parts, causing the
parts to fall or the unit to leak water.
•
Be certain to use electric dampers and shutters to avoid infiltration of cold air, wind and fog
during shutdown in areas with cold climates, strong winds, or where fogs are common.
• Please ensure the product is installed a distance of at least three times the duct diameter away
from exterior wall air inlets, or air exhausts for the prevention of short circuits.
z
Temperature conditions
• Condensation may form on the product when outside air temperature is low, and the temperature
and humidity surrounding the product are high
. Don't intake the air of below 0°C into the fresh air
intake kit.
•The upper limit of the product’s temperature range should respond to the outdoor temperature range.
z
About duct fan
• When installing the duct fan, connect the drive relay
(
Locally purchased
)
and operate with the
indoor unit.
• Please ensure the intake air volume is below 10% of the product’s air volume HI. When
the intaken air volume becomes too large there the operating noise may increase and room
temperature detection may be affected.
z
About the duct connection
•
Procure a duct with internal diameter that fits the external diameter of the duct flange.
•
Please note that regulations of some countries may require the use of a nonflammable duct.
•
If the duct penetrates a fire-retarding division or other fire-proofing measures, the installation
of fire dampers, or a construction that does not adversely affect fire control measures is a
regulatory requirement of some countries.
• When using metallic ducts please ensure metals (i.e., metal lath, wire lath, stainless sheeting) are
electrically insulated. (A short occurring by electrical connection can cause fire)
•Please ensure to thermally insulate connected ducts to prevent condensation.
• Please make certain that netting or other measures are installed in parts exposed to the outside
air to prevent infiltration of small animals such as birds and insects.
•
Please be certain to install external air filters to parts exposed to the outside air for heat
exchanger protection of indoor equipment.
•
Please avoid the infiltration of rain water by installing outside ducts with an incline of at least 1/30,
and fitting hoods on openings.
Summary of Contents for AB* A12GATH
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...
Page 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...
Page 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...
Page 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...
Page 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...
Page 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...
Page 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...
Page 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...
Page 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...
Page 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...
Page 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...
Page 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...
Page 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...
Page 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...
Page 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...
Page 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...
Page 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...
Page 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...
Page 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...
Page 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...
Page 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...
Page 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...
Page 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...
Page 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...