Selection of pipe size
*a
b
b1
c
d
e1
e2
f1
f2
f3
Liquid pipe
12.70
12.70
9.52
9.52
9.52
6.35
6.35
6.35
6.35
6.35
Gas pipe
22.22
22.22
15.88
15.88
15.88
12.70
12.70
9.52
9.52
9.52
Length (m)
Example
75
5
10
5
5
10
5
5
5
5
Pipe size "a" selection : The length that between outdoor unit and first separation tube or
header. (Condition 2)
a = 75 > 70 m
Therefore Liquid pipe must be size up from 9.52 mm to 12.70 mm. (Refer 2-3. PIPE SIZE)
z
Limitation check
Diagram
Example
(m)
Limitation
(m)
Judge
Total pipe length
Total
155
400m or less
OK
Between outdoor unit and farthest indoor unit
a+b+c+f3
110
120m or less
OK
Between the first separation tube and the farthest indoor unit
b+c+f3
30
90m or less
OK
Between outdoor unit and the nearest indoor unit
a+b1
90
5m or more
OK
Between outdoor unit and the first seperation tube
a
75
3m or more
OK
z
Calculation of additional charge refrigerant
1. Calculation of additional amount for pipe length
Liquid pipe size
12.70
9.52
6.35
Additional refrigerant
(kg/m)
0.114
0.058
0.021
Liquid pipe length (m)
80
20
30
A = (0.114 x 80) + (0.058 x 20) + (0.021 x 30) = 10.91 (kg)
2. Factory charged amount
Model
Factory charged
amount (kg)
Outdoor unit
AJ
090
7.5
B = 7.5 (kg)
3. Total refrigerant amount check
C = A + B = 10.91 + 7.5 = 18.41 (kg) < 20.0 (kg) → OK
Check pipe length and height difference between units by comparing with items shown in "2-2.PIPING
LIMITATION".
- (06 - 25) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for AB* A12GATH
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...
Page 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...
Page 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...
Page 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...
Page 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...
Page 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...
Page 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...
Page 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...
Page 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...
Page 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...
Page 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...
Page 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...
Page 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...
Page 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...
Page 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...
Page 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...
Page 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...
Page 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...
Page 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...
Page 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...
Page 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...
Page 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...
Page 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...
Page 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...