OPERATION STATUS
(External output1)
The output for CNB01 (1-2) is ON when the indoor
unit is operating.
The output is off when the unit is stopped.
ERROR STATUS
(External output2)
The output for CNB01 (1-3) is ON when an error
is generated for the indoor unit.
INDOOR UNIT STATUS
(External output3)
The output for CNB01 (1-4) is ON when the indoor
unit fan is operating.
The output is off when the fan is stopped or
during cold air prevention.
The output for CNB01 (1-4) is OFF during
thermostat OFF when DRY mode operation.
AUXILIARY HEATER OUTPUT
(External output4)
Corresponding indoor units: All duct type.
A signal is outputted from Connector when indoor fan and thermostat ON under heating operation.
* Signal output performance specifications are as
shown on the right
Ex. When Set Temperature(Ts) is 22°C
▪ and Room Temperature(Tr) increase above 12°C,
signal output is on.
▪ and Room Temperature(Tr) increase above 21°C,
signal output is off.
▪ and Room Temperature(Tr) decrease below 19°C, signal output is on.
▪and Room Temperature(Tr) decrease below 10°C, signal output is off.
The output also turns OFF on defrost operation and oil recovery operation.
z
Fan delay switch (Indoor Unit)
This is used to continue indoor unit fan
operation for 1 minute after thermo OFF
in heating mode.
1 minute delay control set by Dip sw2-3
on PCB is ON.
CAUTION
Please install auxiliary heater between the indoor unit and the outlet side.
Please be sure to use delay control of a fan.
Please design and install auxiliary properly considering
protection by auxiliary itself.
If auxiliary does not design and install properly, it may cause fire by auxiliary's heat.
In case of auxiliary does not design and install properly, our company cannot take responsibility.
Operation
Stop
12V
0V
CNB01(1-2)
Output
Indoor unit
Error
Normal
12V
0V
CNB01(1-3)
Output
Indoor unit
Fan run
Fan stop
12V
0V
CNB01(1-4)
Output
Indoor unit
Ex) Used for inter lock energize for exhaust fan.
OFF
OFF
ON
Tr-Ts = -1°C
Tr-Ts
Tr-Ts = -3°C
Tr-Ts = -10°C
Tr-Ts = -12°C
ON
OFF
Operation
Stop
Heating
operation
Indoor unit fan
12V
0V
CNB01 (1-5)
output
1min
Auxiliary
Heater
Supply air
Return air
Indoor unit
- (08 - 23) -
E
X
TE
RNAL
IN
PU
T
&
O
U
TP
U
T
E
X
TE
RNAL
IN
PU
T
&
O
U
TP
U
T
Summary of Contents for AB* A12GATH
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...
Page 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...
Page 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...
Page 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...
Page 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...
Page 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...
Page 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...
Page 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...
Page 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...
Page 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...
Page 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...
Page 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...
Page 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...
Page 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...
Page 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...
Page 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...
Page 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...
Page 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...
Page 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...
Page 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...
Page 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...
Page 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...
Page 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...
Page 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...