- (10 - 31) -
O
PT
IONAL
PA
R
TS
O
PT
IONAL
PA
R
TS
5. RB UNIT
5-1. SPECIFICATIONS
Model name
UTP-RX01AH
UTP-RX01BH
UTP-RX01CH
UTP-RX04BH
Power source
1 Phase 230V ~ 50Hz
Available voltage range
198 to 264V
Number of branches
1
1
1
4
Maximum number of connectable indoor units per
branch
3
8
8
8
Maximum capacity of connectable indoor
units(Q)
kW
Q ≤ 8.0
Q ≤ 18.0
Q ≤ 28.0
Q ≤ 56.0 *1
Maximum capacity of connectable indoor
units per branch(Q)
Q ≤ 8.0
Q ≤ 18.0
Q ≤ 28.0
Q ≤ 18.0
Input power
W
17
24
31
96
Running current
A
0.11
0.16
0.22
0.64
Refrigerant type
R410A
Dimensions
(H x W x D)
Net
mm
198×298×268
260×658×428
Gross
262×833×374
348×1250×775
Weight
Net
kg
7
7.5
8
31.5
Gross
9.5
10.5
11
39.5
Connection
pipe
Outdoor
unit side
Suction gas pipe
mm
ø12.70
ø19.05
ø22.22
ø28.58
Discharge gas pipe
ø9.52
ø12.70
ø19.05
ø22.22
Liquid pipe
None
ø15.88
Indoor
unit side
Gas pipe
ø12.70
ø19.05
ø22.22
ø19.05
Liquid pipe
None
ø9.52
Method
Brazing
Operation range
°C
-15 to 46
%RH
80 or less
*1:
In case of two RB units connected in series ( total 8-branches ), maximum capacity of connectable indoor units
is up to 56.0kW.
Summary of Contents for AB* A12GATH
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...
Page 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...
Page 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...
Page 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...
Page 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...
Page 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...
Page 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...
Page 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...
Page 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...
Page 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...
Page 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...
Page 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...
Page 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...
Page 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...
Page 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...
Page 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...
Page 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...
Page 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...
Page 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...
Page 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...
Page 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...
Page 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...
Page 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...
Page 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...