![Fujitsu AB* A12GATH Design & Technical Manual Download Page 957](http://html.mh-extra.com/html/fujitsu/ab-a12gath/ab-a12gath_design-and-technical-manual_117996957.webp)
2-28.
ELECTRICITY CHARGE APPORTIONMENT SETTING
(SYSTEM CONTROLLER, TOUCH PANEL CONTROLLER)
In this section, an electricity charge apportionment function which uses electricity meters is
explained. System Controller (UTY-APGXZ1, UTY-PEGXZ1) or System Controller Lite (UTY-
ALGXZ1, UTY-PLGXA2) or Touch panel controller (UTY-DTG*Z1, UTY-PTGXA) is required to
perform these functions.
ELECTRICITY CHARGE APPORTIONMENT AND ELECTRICITY
METER
When implementing the electricity charge apportionment function in a VRF System, a
configuration which does not use electricity meters or a configuration which uses electricity
meters can be selected. The differences between these two configurations are explained
below.
The electricity charge apportionment function apportions the power consumption to each
block (tenant indoor unit) defined in advance according to the usage record, after the power
consumption (electricity charge) of the air conditioners is input to the System Controller.
Electricity charge apportionment calculation becomes possible only after inputting the power
consumption (or electricity charge).
[Electricity charge apportionment when electricity meter not used]
Only after the electricity bill is received from the electric power company and the billed amount
is input into the System Controller, can electricity charge apportionment for the billed period be
calculated.
[Electricity charge apportionment when electricity meter used]
Since the power consumption data is sent from the electricity meter to the System Controller at
any time, basically electricity charge apportionment calculation can be performed at any time.
Because an actual System Controller calculate power charge apportionment data in one day
units, electricity charge apportionment calculation can be performed at an arbitrary day in one
day units.
Example (1)
When the tenants of a tenant building, etc. are billed for their air conditioning electricity charge
once a month, if the electricity bill arrives from the electric power company each month, the
electricity charge apportionment function can be used without electricity meters because
electricity charge apportionment can be performed based on that bill and the tenants can be
billed. Even if there are tenants moving in and out within a month, appropriate billing can be
performed after the bill was received from the electric power company. However, when the
electricity bill is received from the electric power company once every 3 months, electricity
charge apportionment for 3 months cannot be calculated until the bill is received. In this case,
building owner can only bill the building tenants for air conditioning electricity charges every 3
months. However, if electricity meters are installed, billing at an arbitrary interval, for example,
once a month, is possible.
Example (2)
When air conditioning electricity charge is billed based on the electricity charge apportionment
function for each room in hotels etc., because guests leave and arrive daily and the electricity
charge is calculated each time, you cannot wait for the electricity bill to arrive from the electric
power company. In such cases, it must be possible to be able to calculate electricity charge
apportionment at any time using electricity meter.
- (07-176) -
F
UN
C
TI
O
N
SE
T
TI
N
G
F
UN
C
TI
O
N
SE
T
TI
N
G
Summary of Contents for AB* A12GATH
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...
Page 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...
Page 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...
Page 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...
Page 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...
Page 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...
Page 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...
Page 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...
Page 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...
Page 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...
Page 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...
Page 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...
Page 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...
Page 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...
Page 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...
Page 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...
Page 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...
Page 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...
Page 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...
Page 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...
Page 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...
Page 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...
Page 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...
Page 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...