1-1-1. EXTERNAL INPUT
Setting to "Low noise mode", "Cooling priority/heating priority selection", "Outdoor unit
operation peak control", "Emergency/batch stop" and "Electricity meter pulse" are possible
from the outside.
WIRING METHOD AND SPECIFICATIONS
*A twisted pair cable (22AWG) should be used. Maximum length of cable is 150m.
* Use an external input and output cable with appropriate external dimension, depending on the
number of cables to be installed
*For each input, pin No.1 is of positive polarity and pin No.2 is of ground level.
1 2
1 2
1 2
1 2
1 2
CN131
(Yellow)
Input1
connected unit connected unit connected unit connected unit connected unit
Input2
Input3
Input4
Input5
CN132
(Green)
CN133
(White)
CN134
(Red)
CN135
(Orange)
P.C.B
OPERATION BEHAVIOR
Connector
Input signal
Status
Outdoor unit
Master
Slave
CN131 (Yellow)
OFF
Normal operation
○
ON
Low noise mode operation
CN132 (Green)
*1
OFF
Cooling priority
○
ON
Heating priority
CN133 (White)
OFF
Normal operation
○
ON
Outdoor unit operation peak control
CN134 (Red)
OFF
Normal operation
○
ON
Batch stop or Emergency stop operation *2, *3
CN135 (Orange)
*4
No pulse
No information from electricity meter
○
○
Pulse
Power usage information from electricity meter
Slave unit can connect only input5 (CN135).
Note :
*1: The "external input priority mode" must be set by pressing push button on PC board of outdoor
unit.
*2: Batch stop or Emergency stop pattern can be selected by outdoor unit PC board push button.
*3: The emergency stop function mounted in the equipment does not guarantee the regulations of
each country. For this reason, sufficient checking is necessary regarding use.
Especially, since the fact that the equipment may not be emergency-stopped in the case of
breaking of the wiring to the external input terminals and communication line, communication
error due to noise, VRF external input circuit trouble, etc. must be considered, the provision of
double measures that add direct interruption of the power supply by switch, etc. is recommended
as a precaution.
*4: Pulse input to CN135 must be width 50ms or more, and must be interval 50ms or more.
- (08 - 04) -
E
X
TE
RNAL
IN
PU
T
&
O
U
TP
U
T
E
X
TE
RNAL
IN
PU
T
&
O
U
TP
U
T
Summary of Contents for AB* A12GATH
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...
Page 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...
Page 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...
Page 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...
Page 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...
Page 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...
Page 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...
Page 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...
Page 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...
Page 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...
Page 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...
Page 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...
Page 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...
Page 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...
Page 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...
Page 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...
Page 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...
Page 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...
Page 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...
Page 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...
Page 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...
Page 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...
Page 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...
Page 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...