1-2. CHECKING CONCENTRATION LIMIT
Check concentration limit following steps
, and take appropriate measures depending on
the situation.
Calculate amount of all replenished refrigerant (kg) per refrigerant system.
Smallest room volume.
Calculate room volume by regarding
portion as one room or the smallest room.
Calculate refrigerant concentration from the results of
and
Amount of replenished
refrigerant per refrigerant
system
Amount of additional
replenished refrigerant
Total amount of replenished
refrigerant in refrigerant
system (kg)
+
=
Amount of replenished
refrigerant at factory
shipment
Amount of additionally
replenished refrigerant
depending on piping
length , piping diameter
and indoorunit model at
customer.
Note : When one refrigerant
system is divided into 2 or more
refrigerant systems and each
system is independent, total
amount of replenished refrigerant
of each system shall be adopted.
Total amount of
replenished refrigerant in
refrigerant facility (kg)
When the result of calculation
exceeds the limiting
concentration,perform the same
calculations by shifting to the
second smallest,and the third
smallest rooms until the final result
is below the limiting concentration.
≤Refrigerant concentration (kg/m
3
)
(R410A)
Capacity of smallest
room where indoor unit is
installed (m
3
)
(a) Without partition
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Smallest
room
Indoor unit
Partition
Opening
(b) When there are partitions,
but there is an effective
opening for ventilation between
the rooms.
(d) When a mechanical
ventilation device linked to a gas
leak detection warning device is
mounted in the smallest room.
The room with the second
smallest area is the target.
(c) With partition and without
opening which serve as
passage of air to adjoining
room.
- (09 - 02) -
N
O
TE
S
N
O
TE
S
Summary of Contents for AB* A12GATH
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...
Page 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...
Page 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...
Page 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...
Page 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...
Page 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...
Page 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...
Page 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...
Page 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...
Page 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...
Page 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...
Page 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...
Page 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...
Page 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...
Page 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...
Page 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...
Page 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...
Page 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...
Page 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...
Page 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...
Page 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...
Page 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...
Page 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...
Page 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...