![Fujitsu AB* A12GATH Design & Technical Manual Download Page 141](http://html.mh-extra.com/html/fujitsu/ab-a12gath/ab-a12gath_design-and-technical-manual_117996141.webp)
Note : Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating : Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
Model name
AUXB12GALH
AUXB14GALH
AUXB18GALH
AUXB24GALH
Power source
230 V ~, 50 Hz
Available voltage range
198 to 264 V
Capacity
Cooling
kW
3.6
4.5
5.6
7.1
Heating
4.1
5.0
6.3
8.0
Input power
W
29
35
36
84
Fan
Airflow rate
High
m
3
/ h
(l / s)
600
(167)
680
(189)
710
(197)
1,030
(286)
Med
530
(147)
590
(164)
580
(161)
830
(231)
Low
390
(108)
390
(108)
400
(111)
450
(125)
Type x Quantity
Turbo × 1
Motor output
W
54
Sound
pressure
level
High
dB(A)
37
38
41
50
Med
34
34
35
44
Low
27
27
27
30
Heat
exchanger
Length
mm
1,280
1,295
Fin pitch
1.20
1.30
Rows x Stages
2 × 10
3 × 10
Face Area
m
2
0.27
0.28
Pipe type (Material)
Grooved H-pin (Copper)
Fin
Type (Material)
Slit (Aluminium)
Surface treatment
Hydrophilic coating
Air filter
Type
Anti-mold
Net material
PP honeycomb
Enclosure
Material
galvanized sheet iron
Colour
-
Dimensions
(H x W x D)
Net
Main body
mm
245 × 570 × 570
Gross
265 × 730 × 625
Weight
Net
kg
15
17
Gross
19
20
Connection
pipe diameter
Liquid (Flare)
mm
ø 6.35
ø 9.52
Gas (Flare)
ø 12.70
ø 15.88
Drain hose
VP25 [ø 25(I.D.) ; ø 32(O.D.)]
Cassette grille
(Option)
Model name
UTG-UFYC-W(FUJITSU brand); UTG-UFGC-W(GENERAL brand)
Colour
WHITE
(Approximate colour of MUNSELL N9.25/)
Dimensions
(H x W x D)
Net
mm
50 × 700 × 700
Gross
120 × 765 × 755
Weight
Net
kg
2.6
4.5
Gross
- (04-02) -
IND
OO
R
UN
IT
S
IND
OO
R
UN
IT
S
Summary of Contents for AB* A12GATH
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...
Page 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...
Page 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...
Page 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...
Page 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...
Page 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...
Page 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...
Page 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...
Page 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...
Page 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...
Page 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...
Page 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...
Page 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...
Page 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...
Page 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...
Page 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...
Page 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...
Page 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...
Page 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...
Page 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...
Page 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...
Page 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...
Page 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...
Page 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...