1-1-2. EXTERNAL OUTPUT
Connector
Output voltage
Status
CN136 (Black)
0V
Normal
DC 12-24 V *4
Error
CN137 (Blue)
0V
Stop
DC 12-24 V *4
Operation
ERROR STATUS (Master unit only)
This output indicates the outdoor unit and connected indoor unit's "Normal" or "Error" status.
OPERATION STATUS (Master unit only)
This output indicates the outdoor unit's "Operation" status.
*4: Provide a DC12 to 24V power supply.
Select a power supply capacity with an ample
surplus for the connected load.
*5: The allowable current is 30mA or less.
Provide a load resistance such that the current
becomes 30mA or less.
*6: Polarity is [+] for pin 1 and [-] for pin 2.
Connect correctly.
Do not impress a voltage exceeding 24V across
pins 1-2.
1
2
+
+
-
-
CN136
(Black)
or CN137
(Blue)
connected unit
DC power supply
(External) 12 - 24V
Connected
load (Operation
Indicator or Error
Indicator)
*6
*4
*5
P.C.B
CN137
Output
CN136
Output
Operation
Error
12 - 24V
12 - 24V
0V
0V
Stop
Normal
*A twisted pair cable (22AWG) should be used. Maximum length of cable is 150m.
* Use an external input and output cable with appropriate external dimension, depending on the
number of cables to be installed.
BASE HEATER
This is the output signal for base heater. Output signal ON, when the outdoor temperature
goes down below 2°C, and signal OFF at the outdoor temperature 4°C.
*7: Connect to pin 1 and pin 3. No connection pin2 and pin4.
*8: The allowable current is 1A or less.
1
2
3
4
CN115
(Black)
Voltage: power supply
input voltage
Base heater
*8
*7
P.C.B
AWG18 (0.82mm
2
)
- (08 - 06) -
E
X
TE
RNAL
IN
PU
T
&
O
U
TP
U
T
E
X
TE
RNAL
IN
PU
T
&
O
U
TP
U
T
Summary of Contents for AB* A12GATH
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...
Page 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...
Page 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...
Page 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...
Page 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...
Page 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...
Page 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...
Page 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...
Page 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...
Page 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...
Page 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...
Page 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...
Page 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...
Page 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...
Page 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...
Page 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...
Page 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...
Page 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...
Page 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...
Page 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...
Page 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...
Page 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...
Page 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...
Page 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...