LED105
CODE No.
Setting Mode
LED104
CODE No.
Setting Function
Factory
setting
Outdoor unit
Remarks
Master Slave
2
0
Switching
between
batch stop or
emergency stop
0
0
Batch stop
l
¡
-
*1
This mode selects the pattern of
the stop function to be operated
by the external input terminal
(CN134).
•Batch stop: The stop of all
indoor units connected to same
refrigerant system due to input
signal coming from CN134.
•Emergency stop: When
emergency stop is actuated, the
indoor unit does not accept the
operation command from the
remote controller. On the other
hand, when the emergency
stop is released (no input from
CN134), the air conditioner
does not return to the original
operation until operate indoor
unit by the remote controller.
0
1
Emergency stop
2
1
Operation
mode selecting
method
0
0
Priority given to the
first command
l
¡
-
*1
Select the priority setting of the
operation mode.
•Priority given to the first
command: Priority is given to
the operation mode which is set
first.
•Priority given to external input
of outdoor unit: Priority is given
to the operation mode which is
set by the external input terminal
(CN132).
•Priority given to administrative
indoor unit: Priority is given
to the operation mode of the
administrative indoor unit which
is set by the wired remote
controller.
0
1
Priority given to
external input of
outdoor unit
0
2
Priority given to
administrative indoor
unit
2
2
Snow falling
protection fan
mode
0
0
Enable
l
¡
-
*1
This mode operates the fans
of outdoor units in order to
prevent the units from stopping
operation when they are
covered by snow.
0
1
Disable
2
3
Interval setting
for snow falling
protection fan
mode
0
0
Standard (30minutes)
l
¡
-
*1
When the snow falling protection
fan mode is set, the operation
interval of the fans of outdoor
units can be selected.
0
1
Short1 (5minutes)
0
2
Short2 (10minutes)
0
3
Short3 (20minutes)
2
4
High static
pressure mode
0
0
Standard
l
¡
¡
When installing a duct to the
blow-off outlet of an outdoor
unit, set the high static pressure
mode according to the static
pressure of the duct to be
installed.
Furthermore, use this setting if
the air blow of an outdoor unit is
poor, such as when installed in
a place with a low ceiling.
0
1
High static pressure 1
(equivalent to 30Pa)
0
2
High static pressure 2
(equivalent to 82Pa)
0
3
Prohibited
2
5
Prohibited
0
0
Prohibited
l
Setting prohibited
0
1
Prohibited
*1: Do not set this for outdoor units with Slave setting.
- (07-74) -
F
UN
C
TI
O
N
SE
T
TI
N
G
F
UN
C
TI
O
N
SE
T
TI
N
G
Summary of Contents for AB* A12GATH
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...
Page 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...
Page 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...
Page 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...
Page 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...
Page 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...
Page 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...
Page 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...
Page 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...
Page 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...
Page 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...
Page 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...
Page 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...
Page 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...
Page 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...
Page 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...
Page 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...
Page 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...
Page 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...
Page 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...
Page 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...
Page 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...
Page 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...
Page 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...