3-2. METHOD OF CAPACITY CALCULATION
The capacity calculation method which takes the effects of air temperature, pipe length and
frosting/defrosting into consideration is shown below.
1. Calculate the estimated capacity of each indoor unit.
(1) Find
capacity of indoor unit at rated condition (TCin)r and at design temperature (TCin)d
[from 7. CAPACITY TABLE COOLING (INDOOR UNIT) or 8. CAPACITY TABLE HEATING (INDOOR UNIT)]
(2) Find the following compensation coefficient
[From 6. CAPACITY COMPENSATION COEFFICIENT].
●
Compensation coefficient of pipe length
●
Compensation coefficient of frosting/defrosting
(Heating calculation only
)
(3) Calculate
the estimated capacity of indoor unit (TCin)e.
COOLING:
Estimated capacity of indoor unit (TCin)e
= Capacity of indoor unit at design temperature (TCin)d
x Compensat
ion coefficient of pipe length
HEATING:
Estimated capacity of indoor unit (TCin)e
= Capacity of indoor unit at design temperature (TCin)d
x Compensation coefficient of pipe length
x Compensation coefficient of frosting/defrosting
2. Calculate the compensated capacity of outdoor unit.
(4) Find
capacity of outdoor unit at rated condition (TCout)r
[From 2. MODEL LINE UP].
(5) Calculate
total rated capacity of indoor units : ∑(TCin)r
and
ratio to the rated capacity of outdoor unit : ∑(TCin)r / (TCout)r
.
(6) Find capacity of outdoor unit at design temperature (TCout)d
[using result of (5) and 4. CAPACITY TABLE (OUTDOOR UNIT)].
(7) Calculate the compensated capacity of outdoor unit (TCout)c.
COOLING:
Compensated capacity of outdoor unit (TCout)c
= Capacity of outdoor unit at design temperature (TCout)d
x Compensation coe
fficient of pipe length
HEATING:
Compensated capacity of outdoor unit (TCout)c
= Capacity of outdoor unit at design temperature (TCout)d
x Compensation coefficient of pipe length
x Compensation coefficient of frosting/defrosting
3. Decide system capacity.
(8) Calculate
total capacity of indoor units at design temperature
∑
(TCin)d.
(9)
System capacity
= the smaller one of (TCout)c and
∑
(TCin)d. • • • • • • • •
(7) or (8)
4. Calculate actual capacity of each indoor unit.
(10) Calculate actual capacity of each indoor unit by dividing system capacity proportionally.
Actual capacity of indoor unit
= (System capacity) x (Rated capacity of indoor unit) / (Total rated
capacity of indoor unit )
= (System capacity) x (TCin)r /
∑
(TCin)r • • • • •
(9) x (1) / (5)
- (02 - 09) -
MOD
EL
SE
LE
C
TI
O
N
MOD
EL
SE
LE
C
TI
O
N
Summary of Contents for AB* A12GATH
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION DTV_J3LE050E_03 CHAPTER01 2017 10 31 ...
Page 20: ...2 MODEL SELECTION DTV_J3LE050E_03 CHAPTER02 2017 10 31 ...
Page 115: ...3 OUTDOOR UNITS DTV_J3LE050E_02 CHAPTER03 2017 07 21 ...
Page 119: ... Unit mm Detail B Detail A Detail C 03 03 OUTDOOR UNITS OUTDOOR UNITS ...
Page 128: ...5 WIRING DIAGRAM MODELS AJ 072LELAH AJ 090LELAH 03 12 OUTDOOR UNITS OUTDOOR UNITS ...
Page 129: ... MODEL AJ 108LELAH 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 133: ... SOUND LEVEL CHECK POINT Microphone Airflow 1 m 03 17 OUTDOOR UNITS OUTDOOR UNITS ...
Page 136: ...4 INDOOR UNITS DTV_VR2E018E_14 CHAPTER04 2017 10 31 ...
Page 216: ... Unit mm INSTALLATION PLACE 04 77 INDOOR UNITS INDOOR UNITS ...
Page 233: ... MODELS ARXC72GBTH ARXC90GBTH ARXC96GATH 04 94 INDOOR UNITS INDOOR UNITS ...
Page 234: ...4 9 LARGE AIRFLOW DUCT TYPE MODEL ARXN018GLBH 04 95 INDOOR UNITS INDOOR UNITS ...
Page 235: ... MODELS ARXN024GTBH ARXN030GTBH 04 96 INDOOR UNITS INDOOR UNITS ...
Page 242: ... MODELS AS A012GCAH AS A014GCAH 04 103 INDOOR UNITS INDOOR UNITS ...
Page 245: ... MODELS AS A030GTAH AS A034GTAH 04 106 INDOOR UNITS INDOOR UNITS ...
Page 247: ... MODELS AS E012GCAH AS E014GCAH 04 108 INDOOR UNITS INDOOR UNITS ...
Page 466: ...5 CONTROL SYSTEM DTV_VR2E018E_12 CHAPTER05 2017 10 31 ...
Page 690: ...6 SYSTEM DESIGN DTV_J3LE050E_03 CHAPTER06 2017 10 31 ...
Page 779: ...7 FUNCTION SETTING DTV_VR2E018E_14 CHAPTER07 2017 10 31 ...
Page 975: ...8 EXTERNAL INPUT OUTPUT DTV_VR2E018E_11 CHAPTER08 2017 10 31 ...
Page 1016: ...9 NOTES DTV_VR2E018E_11 CHAPTER09 2017 07 21 ...
Page 1034: ...10 OPTIONAL PARTS DTV_VR2E018E_13 CHAPTER10 2017 10 31 ...
Page 1068: ... 10 33 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH Unit mm ...
Page 1073: ... 10 38 OPTIONAL PARTS OPTIONAL PARTS 5 5 WIRING DIAGRAMS MODEL UTP RX01AH MODEL UTP RX01BH ...
Page 1074: ... 10 39 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX01CH ...
Page 1075: ... 10 40 OPTIONAL PARTS OPTIONAL PARTS MODEL UTP RX04BH ...