6.1 Common Specifications
6-5
Chap. 6
CO
NTR
O
L O
P
TIONS
6.1.2.2 Operating
environment
Options are designed for use in the same operating environment as the FRENIC-VG.
Table 6.1.5 Operating Environment
Item Specifications
Installation location
Shall be free from corrosive gases, flammable gases, oil mist, dusts, and direct sunlight.
(Pollution degree 2 (IEC60664-1)). Indoor use only.
Ambient
temperature
-10 to +50°C (-10 to +40°C when installed side-by-side without clearance (22 kW or
below))
Relative humidity
5 to 95% RH (without condensation)
Altitude
3,000 m or below
1001 to 3000 m: Current derating is required for use.
Refer to the Chapter 3, 3.3 "Mounting and Wiring the Inverter."
Vibration
200 V 55 kW, 400 V 75 kW or below
3 mm: 2 to less than 9 Hz,
9.8 m/s
2
: 9 to less than 20 Hz
2 m/s
2
: 20 to less than 55 Hz
1 m/s
2
: 55 to less than 200 Hz
200V 75 kW, 400 V 90 kW or above
3 mm: 2 to less than 9 Hz
2 m/s
2
: 9 to less than 55 Hz
1 m/s
2
: 55 to less than 200 Hz
Note: Use of options in an operating environment that does not satisfy these conditions may result in
decreased performance and service life or equipment failure.
Summary of Contents for FRENIC-VG Series
Page 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Page 2: ......
Page 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Page 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Page 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Page 344: ......
Page 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...