6.15 E-SX Bus Interface Card
6-261
Chap. 6
CO
NTR
O
L O
P
TIONS
6.15.8 Format
details
6.15.8.1
I area (MICREX-SX
←
FRENIC-VG)
(1) Standard format 2 (U11 = 3)
1
Polling function code address, polling function code data
(MSB)
(LSB)
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Polling function code 485No (1)
Polling function code 485No (2)
Data of polling function code (1)
Data of polling function code (2)
The 485No corresponding to the function code in the polling request from the MICREX-SX is
stored in "Polling function code 485No (1), (2)" (16 bits). The data are respectively stored in "Data
of polling function code (1), (2)".
2
Function code monitor
(MSB)
(LSB)
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Data of function code monitor (1)
Data of function code monitor (2)
"Function code monitor (1), (2)" are constant monitors of function code data. Set the 485Nos. of
the function codes to be monitored in function code o160 for "Function code monitor (1)" and o161
for "Function code monitor (2)".
3
Motor speed
(MSB)
(LSB)
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Motor speed (decimal) x 20000 ÷ maximum speed
⇒
16 bit data
The maximum speed is the speed set in inverter function code F03. To use r/min units, calculate
the above equation in reverse. When the data is negative (2's complement), the command becomes
a reverse speed command.
Summary of Contents for FRENIC-VG Series
Page 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Page 2: ......
Page 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Page 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Page 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Page 344: ......
Page 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...