![Fuji Electric FRENIC-VG Series User Manual Download Page 232](http://html1.mh-extra.com/html/fuji-electric/frenic-vg-series/frenic-vg-series_user-manual_2341868232.webp)
6-156
Table 6.7.3 LED status indicator specifications
Status
L.RUN L.ERR
SD
RD
Operation Status
●
○
★
●
Normal communications
●
★
★
●
Normally communicating. But sometimes a CRC error occurs
due to electrical noise.
●
★
○
●
Received data contains a CRC error, so the communications
card cannot respond.
●
○
○
●
Data destined for this station does not come.
○
★
★
●
Responding to polling. But refresh data received contains a
CRC error.
○
★
○
●
Data destined for this station contains a CRC error.
○
○
○
●
No data destined for this station. Or data destined for this
station cannot be received due to electrical noise.
○
●
○
●○
Baud rate, station address incorrectly specified.
●
★
(0.8-second
intervals)
★
●
Baud rate or station address changed before completion.
○
○
★
●
Link has not been started up.
○
○
○
○
Data cannot be received due to wire break, power down,
hardware reset in progress,
er3
power area failure
●
: ON,
○
: OFF,
★
: Blinking (It may seem to be ON depending on the current transmission baud rate.)
Note 1: If LED lights due to a pattern other than the above, it can be assumed hardware error has occurred.
Contact us.
Summary of Contents for FRENIC-VG Series
Page 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Page 2: ......
Page 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Page 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Page 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Page 344: ......
Page 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...