![Fuji Electric FRENIC-VG Series User Manual Download Page 44](http://html1.mh-extra.com/html/fuji-electric/frenic-vg-series/frenic-vg-series_user-manual_2341868044.webp)
5-24
Selecting response frame
[Inverter
J
Host]
0
1 2
3
4
5
6 7
SOH
Station No.
ACK/NAK
Command
ETX
BCC
1
2 1
1
1 2
(byte)
Values
Byte Field
ASCII format
Hexadecimal format
Description
0 SOH
SOH
01
H
Transmission
begins
1
'0' - '3', '9'
30
H
- 33
H
, 39
H
Inverter station address (Decimal: tens place)
2
Station No.
'0' - '9'
30
H
- 39
H
Inverter station address (Decimal: ones place)
Transmission
response
ACK 06
H
3 ACK/NAK
NAK 15
H
Positive response: No receiving error or request logic error
Negative response: Request logic error
Request
command
'a' 61
H
Speed setting 1 (S01)
'b' 62
H
Torque
command
(S02)
'c' 63
H
Torque current command (S03)
'd' 64
H
Magnetic flux command (S04)
'e' 65
H
Orientation position command (S05)
'f' 66
H
Run command (S06)
4 Command
'm' 6D
H
Reset command: All "0"
5 ETX
ETX
03
H
Transmission
ends
6
'0' - '9', 'A' - 'F'
30
H
- 39
H
, 41
H
- 46
H
Sum-check 1 (Hexadecimal: tens place)
7
BCC
'0' - '9', 'A' - 'F'
30
H
- 39
H
, 41
H
- 46
H
Sum-check 2 (Hexadecimal: ones place)
BCC target
Summary of Contents for FRENIC-VG Series
Page 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Page 2: ......
Page 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Page 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Page 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Page 344: ......
Page 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...