6.7 CC-Link Interface Card
6-171
Chap. 6
CO
NTR
O
L O
P
TIONS
6.7.8.3
Monitor code/command code (o32=0) in VG7 compatible mode
Table 6.7.17 Monitor Code (o32 = 0)
Code No.
Description
Unit
Remarks
0000
H
No monitoring (Fixed to 0)
-
0001
H
Output frequency
0.01 Hz
In units of 0.1 Hz
0002
H
Output
current
0.1
A
0003
H
Output
voltage
0.1
V
0004
H
No monitoring (Fixed to 0)
-
0005
H
Speed setting
1 r/min
0006
H
Operation speed
1 r/min
0007
H
Torque
command
value
0.1%
0008
H
DC link bus voltage
0.1 V
In units of 1 V
0009
H
|
000D
H
No monitoring (Fixed to 0)
000E
H
Motor output
0.01 kW
In units of 0.1 kW
000F
H
Operation
command
-
0010
H
Output terminate status
-
0011
H
Torque current command value
0.1%
0012
H
Flux
command
0.01%
0013
H
Position detection pulse
1 pulse
Quad multiplication of built-in PG
0014
H
Cumulative run time (Cumulative power-ON
time)
1 hr
0015
H
|
0019
H
No monitoring (Fixed to 0)
Detailed description on operation command
b15
b8
b7
b0
RST X14 X13 X12 X11 X9 X8
X7
X6
X5
X4
X3
X2
X1
REV FWD
Figure 6.7.14
Detailed description on output terminate status
b15
b8
b7
b0
Y18 Y17 Y16 Y15 Y14 Y13 Y12 Y11
-
-
- Y5A
Y4
Y3
Y2 Y1
- : Empty (Fixed to 0)
Figure 6.7.15
Summary of Contents for FRENIC-VG Series
Page 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Page 2: ......
Page 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Page 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Page 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Page 344: ......
Page 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...