6-248
6.14.6 Operation
method
The encoder (1) and NTC thermistor (1) will be connected when the SEL terminal of the terminal block
and the 0-V external power supply terminal are open.
The encoder (2) and NTC thermistor (2) will be connected when the SEL terminal of the terminal block
and the 0-V external power supply terminal are closed.
Table 6.14.4
SEL terminal
Encoder and NTC thermistor connected
OFF
Encoder (1) and NTC thermistor (1)
ON
Encoder (2) and NTC thermistor (2)
• No functions are incorporated to change over the motor power wires (U, V, and W). Use a magnetic contactor
(MC) to change them over externally.
• Never make connection changes while the motor during conduction.
Otherwise, the motor may go out of control or the inverter may malfunction.
• The PG signal common terminal (PGM) and thermistor common terminal (THC) are isolated from each other.
Do not short-circuit them with external wires.
• Do not use more than one unit to change over three or more motors. (The power supply to the PG is not
changed over. Therefore, the current may exceed the PG current capacity limit of the inverter.)
Otherwise, the inverter may be damaged.
Summary of Contents for FRENIC-VG Series
Page 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Page 2: ......
Page 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Page 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Page 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Page 344: ......
Page 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...