6.5 SX Bus Interface Card
6-113
Chap. 6
CO
NTR
O
L O
P
TIONS
[ 1 ]
System definition window
In system definition, you construct the system using the SX bus
,
configure the entire system for operation
,
configure operation
,
and configure individual modules. Double-click the [System_Definition] icon in the
[Physical Hardware] configuration subtree to open the system configuration definition screen.
Figure 6.5.28
[ 2 ]
Adding a module
If the transmission format settings are different
,
a heavy alarm occurs and communication is not available. Be
sure to check the following for the correct settings.
For the MICREX-SX series
,
it is necessary to register all the modules (including the inverter) to use in the
system configuration definition of the PC system.
To add the module (inverter), right-click the base module on the system configuration definition tree, and
select [Insert] to open the [Module insert] dialog box.
Figure 6.5.29
System Configuration Definition Tree
Set the SX bus
station address.
Set each item and click the [OK] button.
Module attribute: Individual module
Module type: Select the inverter.
Select the transmission format of FRENIC-VG.
Summary of Contents for FRENIC-VG Series
Page 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Page 2: ......
Page 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Page 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Page 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Page 344: ......
Page 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...