![Fuji Electric FRENIC-VG Series User Manual Download Page 341](http://html1.mh-extra.com/html/fuji-electric/frenic-vg-series/frenic-vg-series_user-manual_2341868341.webp)
6.15 E-SX Bus Interface Card
6-265
Chap. 6
CO
NTR
O
L O
P
TIONS
(4) Toggle
monitor
Performing data toggle monitor between the MICREX-SX and inverter. This example describes
how to set the X12 terminal to TGL1 and the X13 terminal to TGL2.
*1
Set E11 = 72 (TGL1), E12 = 73 (TGL2), H30 = 3, and H144 = 0.10 (100 ms) in advance.
As
a
result,
Transmission toggle (MICREX-SX
→
VG1): %QW254.0.10.13 bit 12 = TGL1, bit 13 = TGL2
The inverter monitors the toggle pattern sent from the MICREX-SX while the run command is ON,
and if the correct toggle signal is not received within the time set in H144, generates toggle error
arf
.
*1 For details on toggling, refer to the E01 to E13 toggle signal section in Chapter 4, Section 4.3 "Details of
Function Codes."
Inverter function code H107 can be set to display
l-al
and continue operation when an alarm
occurs. Refer to the explanation of H107 in
Chapter 4, Section 4.3 "Details of Function Codes."
When F26 "Carrier frequency" is set to a value other than 4 or 8, set the tact cycle of the
application that sends the MICREX-SX transmission toggle to 0.5 ms or higher.
%QW254.0.10.13 * 0 0
0
0
→
1
→
2
→
3
→
0... is sent to * (toggle pattern transmission)
↓
After toggle transmission
%QW254.0.10.13 * 0 0
1
Run command (FWD) = ON
Note: If an
er4
E-SX bus communication error (light alarm, heavy alarm 1) occurs during toggle
transmission and toggle transmission is continued, an
arf
toggle error may occur immediately
after communication recovers normally. To avoid an
arf
toggle error, stop toggle transmission
when an
er4
E-SX bus communication error occurs.
Summary of Contents for FRENIC-VG Series
Page 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Page 2: ......
Page 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Page 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Page 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Page 344: ......
Page 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...