5-34
5.3.2 Transmission
frame
The transmission frame is as follows.
1 byte
1 byte
max. 203 bytes
2 bytes
Station address
FC (function code)
Information
Error check
(1) Station address (station number)
Station addresses
0 to 247
are selectable with a 1 byte length.
Selecting a "0" address selects all slave stations and, therefore, the message will be a broadcast
message.
(2) FC (function code)
Function codes are defined with values of 0 to 255 with a length of 1 byte, as shown below. The
shaded sections indicate codes used with FRENIC-VG. Do not use "unused" function codes. Doing
so will result in an error response being returned.
FC Description
0 to 2
Unused
3
Read function code
Data size: max. 99
4 to 5
Unused
6
Write function code Data: 1
7 Unused
8
Maintenance code
9 to 15
Unused
16
Continuously write function code
Data size: max. 16
17 to 127
Unused
128 to 255
Reserved for Exception Response
(3) Information
Information fields contain all information items (function code, byte count, data size, data, etc.). For
details on information fields for each message type (broadcast, query, normal response, error
response), refer to Section 5.3.2.1 "Reading function codes", Section 5.3.2.2 "Writing single
function codes", and Section 5.3.2.3 "Writing multiple function codes".
(4) Error check
Error check fields contain data 2 bytes in length for the CRC-16 check method.
Because information fields vary in length, it is necessary to calculate the frame length required to
calculate the CRC-16 code from the FC and byte count data.
Summary of Contents for FRENIC-VG Series
Page 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Page 2: ......
Page 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Page 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Page 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Page 344: ......
Page 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...