Error code Error
argument
Cause
Remedy
continuous
regular
flashing
1 pulse
0 pulses
1 pulse
0 pulses
Problems with electromagnetic
compatibility (EMC)
EEPROM check sum error
Inline code buffer overflow.
Too many entries in the table
Set manufacturer’s setting with
the KS2000
Check power supply for under-
or overvoltages
Implement EMC measures
If there is a K bus error, the
error can be localised by
restarting the field bus coupler
(switching it off and on again)
Insert fewer terminals
2 pulses
Unknown data type
Update field bus coupler
software
2 pulses
Programmed configuration
Incorrect table entry/bus
coupler
Check that programmed
configuration is correct
n pulses
(n>0)
(Terminal n) table comparison
incorrect
Incorrect table entry/bus
coupler
3 pulses
0 pulses
Terminal bus command error
No terminal inserted, connect
terminal
A terminal is faulty
Disconnect half the terminals
and check whether the error
recurs. Continue this process
until the faulty terminal is
located
Terminal bus data error
Check whether the n+1
terminal is correctly inserted,
replace if necessary
n pulses
Break behind terminals
(0:coupler)
Check whether the end terminal
KL9010 is inserted
4 pulses
0 pulses
5 pulses
n pulses
Terminal bus error during
register communication with
terminals
Replace terminals
0 pulses
Operating status
LEDs
(continued)
Check sum error in program
flash.
Restore manufacturer’s setting
with the KS 2000
n pulses
The bus terminal n does not
correspond with the
configuration that existed when
the boot project was created
Restore manufacturer’s setting
with the KS 2000, this deletes
the boot project
9 pulses
0 pulses
13 pulses
0 pulses
K bus runtime command error One bus terminal faulty. Halve
the number of bus terminals
and check the remaining bus
terminals for errors. Repeat this
process until the faulty bus
terminal is localised.