8
01 2
34
567
8
9
01 2
34
567
8
9
Set slave address using the two rotary selector switches.
Default setting = 11
All addresses are permitted, each address may only appear once on the network.
1.
Ensure that all devices and components have been switched off and disconnected
from the mains
2.
Ensure that the interface has been disconnected from the mains
3.
Move switch to desired position using a screwdriver.
-
Values on the upper switch represent units
-
Values on the lower switch represent tens
Important!
Ensure that the switches engage properly
x 1
x 10
Example
Setting address 34:
-
Upper rotary selector switch: 4
-
Lower rotary selector switch: 3
Connecting and
configuring the
field bus coupler
(continued)
Slave address
configuration
For the TS/TPS, MW/TT series:
8.
Connect the LocalNet plug on the interconnecting hosepack to the LocalNet connec-
tion on the interface
For the TSt series:
8.
Connect the LocalNet plug on the interconnecting hosepack to the LocalNet OUT
connection
9.
Connect the LocalNet connection on the power source to the LocalNet IN connection
on the interface using a LocalNet cable
4.
Using the original screws, fit the interface lid back into its original position
In systems with more than two power sources, wire the power sources in parallel.
NOTE!
In order to avoid reflections and any transmission problems, fit resistors
to both ends of the field bus cable.
Important!
Before starting up, check that the shield is connected to the robot earth.
Power source 1
RxD/TxD-P (3)
DGND (5)
Power source 2
RxD/TxD-N (8)
RxD/TxD-P (3)
DGND (5)
RxD/TxD-N (8)
DIN rail
DIN rail
Shield
Profibus pin assignment