![Fronius Profibus Operating Instructions Manual Download Page 49](http://html1.mh-extra.com/html/fronius/profibus/profibus_operating-instructions-manual_2339325049.webp)
9
EN
Data transmission properties
Network topology
Linear bus, active bus termination at both ends, spur lines are possible
Medium
Screened twisted-pair cable, must be screened
Number of stations
32 stations in each segment without repeater.
With repeaters can be extended to 127
Max. bus length without repeater
100m at 12 MBit/s. Cable A: 200 m at 1500 KBit/s, up to 1.2 km at 93.75 KBit/s
Max. bus length with repeater
By using repeaters, the maximum bus length can be increased to around 10 km. There
should be at least 3 repeaters and, depending on the manufacturer, there can be up to
10.
Transmission speed
9.6; 19.2: 93.75; 187.5; 500; 1500 KBit/s, up to 12 MBit/s is set automatically
Connector
9-pin D-sub connector
Process data width
Profibus (4,100,231,4,100,233) 112 bit (standard configuration)
Twin Profibus (4,100,403) 176 bit (standard configuration)
Process data format
Motorola
Network topology
Subring
Medium
APF (plastic) fibre (Z1101)
min/max lengths between two stations
Coordinator - Station:
Lmin = 1m
Lmax = 34m
Station - Station:
Lmin = 1m
Lmax = 25m
Station - coordinator:
Lmin = 0m
Lmax = 46m
Number of stations
93.75 kBaud: 13
187.5 kBaud: 12 500 kBaud: 12
1500 kBaud: 10
Transmission speed
93,75
187,5
500
1500 KBit/s
Switch setting
S1 = 0, S2 = 0
S1 = 0, S2 = 0
S1 = 0, S2 = 0
S1 = 0, S2 = 0
Bus connection
2 x HP Simplex
Process data width
Profibus LWL (4,100,232)
112 Bit
RS 485 transmis-
sion technology
LWL networks