
Remote Control
Users Guide
2-10
Table 2-6. STATus:QUEStionable:VOLTage Register Bits
Bit No.
Description
0 INPut2
OVERrange
1 INPut4
OVERrange
2 INPut6
OVERrange
3 INPut8
OVERrange
4 INPut10
OVERrange
5 INPut12
OVERrange
6 to 7
These bits are not used.
8 INPut2
UNDERrange
9 INPut4
UNDERrange
10 INPut6
UNDERrange
11 INPut8
UNDERrange
12 INPut10
UNDERrange
13 INPut12
UNDERrange
14
This bit is not used.
15
This bit is always 0.
Application of the Status Reporting System
To effectively use the status reporting system, the information contained there must be
transmitted to the controller and further processed there. There are several methods that
are represented in this section. Detailed program examples are found in Chapter 6.
Service Request, Making Use of the Hierarchy Structure (GPIB only)
Under certain circumstances, the instrument can send a service request (SRQ) to the
controller. Usually this service request initiates an interrupt at the controller, to which the
control program can react with corresponding actions. An SRQ is always initiated if one
or several of bits 2, 3, 4, 5 or 7 of the status byte are set and enabled in the SRE. Each of
these bits combines the information of a further register, the error queue or the output
buffer. The corresponding setting of the ENABle parts of the status registers can achieve
that arbitrary bits in an arbitrary status register initiate an SRQ. In order to make use of
the possibilities of the service request, all bits should be set to 1 in enable registers SRE
and ESE.
Use of command “*OPC” to generate an SRQ. While waiting for the SRQ, the program
may perform other tasks.
•
Set bit 0 in the ESE (Operation Complete)
•
Set bit 5 in the SRE (ESB)
After its settings have been completed, the instrument generates an SRQ. The SRQ is the
only possibility for the instrument to become active on its own. Each controller program
should set the instrument in a way that a service request is initiated in the case of
malfunction. The program should react appropriately to the service request. A detailed
example for a service request routine is in Chapter 6.
Summary of Contents for NORMA 4000 Operators
Page 6: ...Remote Control Users Guide iv ...
Page 8: ...Remote Control Users Guide vi ...
Page 10: ...Remote Control Users Guide viii ...
Page 26: ...Remote Control Users Guide 2 2 ...
Page 38: ...Remote Control Users Guide 3 2 ...
Page 50: ...Remote Control Users Guide 4 2 ...
Page 150: ...Remote Control Users Guide 4 102 ...
Page 152: ...Remote Control Users Guide 5 2 ...
Page 160: ...Remote Control Users Guide 6 2 ...
Page 184: ...Remote Control Users Guide 6 26 ...