4.0 CONFIGURATION MENU
4-24
CyberCat 254/1016 Programming Manual
Rev 3, 08/2013
P/N: 06-539
4.3.4 HOW TO MODIFY DAYTIME SENSITIVITY SETTINGS
The Daytime Sensitivity Menu provides smoke sensors the ability to have two separate alarm thresholds; one
less sensitive during standard operational hours and one more sensitive during non-operational hours. Each
smoke sensor has two alarm sensitivity thresholds (Night & Day). The Night alarm level is used on all
sensors as the default setting. The Day alarm level is only used if daytime or holiday schedules are set.
From the “Configuration Menu 2” screen, press the F4 key to access the “Daytime Sensitivity Menu”, as
shown below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
F 1 - D A Y T I M E
S E N R A N G E
B
F 2 - S E L E C T
H O L I D A Y S
C
D
Exhibit 4-35: Daytime Sensitivity Menu
F1
= Daytime Sensitivity Range Screen
F2
= Daytime Sensitivity Holidays Screen
4.3.4.1
HOW TO SET DAYTIME SENSITIVITY RANGE
If your system is using the daytime sensitivity option, the On and Off times and the days of the week that the
daytime sensitivity setting is to be used must be configured. Sensors enabled for daytime sensitivity will
change to Day Alarm level when the start time is reached and revert back to Night Alarm level when the stop
time is reached.
From the “Daytime Sensitivity Menu” screen, press F1 to access the “Daytime Sensitivity Range” screen, as
shown below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
D A Y T I M E
S E N S I T I V I T Y
B
S T A R T :
H H : M M A M
C
S T O P : H H : M M P M
D
D A Y O F
W E E K :
S M T W R F S
Exhibit 4-36: Daytime Sensitivity Range Screen
•
Row B - This field allows you to set the Daytime sensitivity start time: Hour (HH), Minute (MM),
AM/PM. Use the
◄►
arrow keys to position the cursor under the field; then use the +/- keys to
increment/decrement the value at the field.
•
Row C - This field allows you to set the Daytime sensitivity stop time: Hour (HH),Minute (MM),
AM/PM. Use the
◄►
arrow keys to position the cursor under the field; then use the +/- keys to
increment/decrement the value at the field.
•
Row D - This field allows you to set the Days of the week that will utilize the Daytime sensitivity
option. Use the
◄►
arrow keys to position the cursor under the field; then use the +/- keys to turn
ON letter representing the day of the week. Toggle letter OFF if it stays with night sensitivity all day.
Summary of Contents for CyberCat 10-064