4.0 CONFIGURATION MENU
4-32
CyberCat 254/1016 Programming Manual
Rev 3, 08/2013
P/N: 06-539
B. HOW TO ASSIGN AUDIO MESSAGES TO AN AMPLIFIER
The Message Configuration screen allows you to assign which panel state(s) will activate the amplifier and
which audio message (1 – 16) will be played in response to each panel condition.
From the “Amplifier Menu” screen, press the F2 key to access the “Message Configuration” screen, as shown
below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
A M P : 0 2
E V A C : E
A L R T : E
B
C O N D I T I O N : A L A R M
C
M E S S A G E
N U M s :
0 0 / 0 0
D
S P E A K E R S : - - - -
S I L : N
Exhibit 4-50: Amplifier Message Configuration Screen
•
Row A (AMP) - This field allows you to select the peripheral bus address of the amplifier. The
address can be changed, but will only change to addresses where the peripheral type is Amplifier.
•
Row A (EVAC & ALRT) – These fields allow you to select the highest state allowed to be reached by
the amplifier automatically when a zone assigned to this amp has been put into the alarm state via
an automatic means (sensor, manual pull, VESDA, etc.).
E
= (enabled) and
D
= disabled.
Dual channel disabled = EVAC and ALERT should be enabled
Dual channel EVAC = EVAC and ALERT enabled
Dual channel ALERT = EVAC disabled and ALERT enabled
•
Row B – This field allows you to select the panel condition (Process, Supervisory, Test Alarm,
Alarm, Alert, Evacuate, Drill or Page) that the audio messages IDs identified in Row C will be
assigned to. The conditions are listed from lowest to highest priority.
•
Row C – This field allows you to set the audio message ID (0-16) that will be played for the panel
condition selected on Row B. Two different audio messages can be set for each panel condition
available in Row B. Each amplifier can store up to 16 messages, each 30 seconds long.
•
Row D (Speakers) - This range of fields allows you to set which of the four speaker circuits available
on the amplifier will activate for each panel condition available in Row B.
-
= not used
1,2,3,4
= Indicates all four speaker circuits active
L
Note:
Do NOT select speaker circuits for EVAC and PAGE conditions if the amplifier is being
used for dual-channel operation. Speaker circuit selection will be made in the “Speaker Circuit
Configuration” screen.
•
Row D (Sil) - This field allows you to set whether the amplifier speaker circuits can be Silenced (Y =
Yes /
N
= No) for each panel condition available in Row B. If nonsilenceable, the speaker circuits
remain active until the system is reset.
Use the
◄►
arrow keys to position the cursor under the appropriate field; then use the +/- keys to toggle
the field status.