4.0 CONFIGURATION MENU
CyberCat 254/1016 Programming Manual
4-29
P/N: 06-539
Rev 3, 08/2013
4.4.1.1 HOW TO CONFIGURE PERIPHERAL DEVICES
The peripheral configuration screen allows you to modify the basic operating parameters of any of the
peripheral devices connected to the panel’s RS485 peripheral bus. Detailed programming of each peripheral
device is accomplished using the panel’s configuration software C-Linx.
From the “Peripheral Menu” screen, press the F1 key to access the “Peripheral Configuration” screen, as
shown below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
P E R I P H E R A L
A D D R : 0 2
B
T Y P E :
R E M
D I S P
1 4 K E Y
C
S U P E R V I S E :
Y E S
Z : 0 0 0
D
P E R I P H E R A L
M S G
0 2
Exhibit 4-44: Peripheral Configuration Screen
•
Row A - This field allows you to select the Peripheral address (2-32, DACT at address 2, if used) of
the device to be modified. Use the
◄►
arrow keys to position the cursor under the field; then use
the +/- keys to increment/decrement the value at the cursor. Press the F4 key to display the
firmware version of the selected device on Row C & D.
•
Row B - This field displays the type of RS485 Peripheral device programmed at the address
displayed in Row A. Use the
◄►
arrow keys to position the cursor under the device type menu;
then use the +/- keys to change to any one of the following peripheral device types:
•
Remote Display 14 Key
•
Ethernet Port
•
Fire-Phone Int***
•
256 LED Graphic*
•
Remote Display 10 Key
•
6 Zone Voice Evac**
•
Zone Graphic
•
Remote Display 2 Key
•
Digital Paging
•
Print Serial
•
Smoke Control**
•
Relay Control
•
Bosch DACT
•
Switch – 20 Zone**
•
Class A Module
•
Print Parallel
•
Annunciator – 20 Zone**
•
Remote MIC
•
Print + Gateway
•
Computer (Precise Vision)
•
Gateway Only
•
Amplifier***
*Press the F1 key to display additional configuration options. See 4.4.1.1.2.
**Press the F1, F2 or F3 keys to perform peripheral device tests. See 4.4.1.1.1.
***Press ENTER to display additional configuration options. See 4.4.1.1.3.
Detailed programming of each peripheral device is set using the panel configuration software C-Linx.
•
Row C - The SUPERVISED field allows you to turn on/off supervision of the RS485 peripheral
device/address shown in Rows A and B (Yes/No). Use the
◄►
arrow keys to position the cursor
under the field; then use the +/- keys to toggle the status of the field.
L
Note:
When a peripheral device is supervised and communications is lost between the
peripheral and the panel, a Peripheral Missing trouble will result.
L
Note:
Peripheral devices with control capabilities must be supervised (i.e., Remote display with
reset button).
The zone field (Z:) only applies to Cheetah Xi releasing panels and associated remote displays.
Configuration of this field will have no effect on a CyberCat system.
•
Row D - This range of fields allows you to enter a 20 character custom message for the peripheral
device listed in Row B. Use the
◄►
arrow keys to position the cursor under the field; then use the
+/- keys to cycle through all ASCII characters and display the desired character.
L
Note:
This message will be displayed with each event associated with the selected peripheral.